Unitary Products Group

3

The new thermostat requires a thermostat cable with a mini-
mum of 10 conductors that run from the sub-base to the con-
trol box. The new wire will be connected as shown in Figure
3.

1.

Locate the W7400 control module in the box-electric
(Figures 1 and 2).

2.

Remove the following wires form the W7400 control
module and from the unit.

201/R

208/BR

254/GY

252/Y

257/Y

248/GY

240/Y

244/0

246/PR

NOTE: Wire ties will need to be removed to remove above
wires.

3.

Disconnect wire 204/BR from the TR terminals on the
w7400 control module.

NOTE: These wires will be used with the new controls.

4.

Disconnect thermostat wire from terminals 1-4 on the
W7400 control module.

NOTE: This wire will be used with the new controls.

NOTE: STEPS 5 THROUGH 7 ARE FOR OPTIONAL HEAT
ONLY.

TABLE 3: PARTS SUPPLIED FOR CV UNITS WITH

OPTIONAL HEAT

QTY

PART NO.

DESCRIPTION

1

373-18689-610

820/Y

823/Y

1

373-18689-611

822/BR

826/BR

1

AB144GRA7171844

844/GY

1

AB144WHT7171845

845/W

2

024-24116-000

Isolation Relay

FIGURE 1: POWER & CONTROL WIRING

LOCATION

FIGURE 2 : EXISTING CONTROL PANEL COMPO-

NET LOCATION

FIGURE 3 : TYPICAL THERMOSTAT WIRING

OPEN ALL DISCONNECTS BEFORE SERVIC-
ING THIS UNIT.