Characteristics, Pulsar evolution 2200 – MGE UPS Systems 500 User Manual

Page 4

Advertising
background image

Pulsar Evolution UPS

500

800

1100

1500

2200

Power VA/W

500/350

800/560

1100/700

1440/1000

1920/1540

Versions

1U Rack

Mini-Tower and 1U Rack

Versatile Tower/2U Rack

Installation possibilities

Rackable, stackable,

Mini-Tower version: vertical or horizontal

Rackable, stackable or

vertical tower

Rack version: rackable or stackable

vertical tower w support base

or wall-mount

Number of outlets

4

4

4

4

6

Including Powershare outlets

2

2

2

2

2

Battery extension (EXB modules)

From 1 to 3 EXBs

Performance

Technology

High-Frequency Line-Interactive

Automatic voltage regulation

Booster/Fader

Output voltage waveform

Sinewave

Input voltage tolerances

92V/138V, adjustable to 80V/153V via supplied UPS-Driver software

Frequency

50/60 Hz, auto-select

Output voltage on battery power

120VAC (adjustable to 100/120/127V via supplied UPS-Driver software)

Input Connection

NEMA 5-15 straight plug, 6 foot cord

NEMA 5-20P

Output Connection

NEMA 5-15

Features

Automatic battery test

Weekly (interval adjustable via supplied UPS-Driver software)

Hot swappable batteries

x

x

x

x

x

Cold start

x

x

x

x

x

Deep discharge protection

x

x

x

x

x

UPS-Driver for Windows

Settings: Input voltage tolerances, Sensitivity, Battery test, ON/OFF conditions

Data line protection

Surge protection for RJ45 network connection

Network Administration/Monitoring

Communications

1 USB port + 1 Serial port

Software supplied (Solution-Pac CD)

Including local power management software and SNMP proxy-agents for Windows 2000/NT/98

Linux, Netware, OpenServer, Unixware, SUN Solaris, IBM AIX, HP UX, Compaq Tru64, etc.

Communication Expansion Slot

1 slot for optional Network Management Card (66246) or status indication card

Standards/Warranty

Safety

EN 50091-1-1/EN60950(RD),IEC 60950,TÜV GS-Mark

Electromagnetic compatibility

EN 50091-2,EN 50022/B,IEC 62040-2,IEC 61000-3-2,IEC 61000-3-3

Design, production and services

ISO 9001

Marking

UL, cUL, FCC Class A, UL1778

Warranty (U.S. and Canada)

2 years, parts and labor

Effective: February 2005

©MGE UPS SYSTEMS, Inc. All specifications subject to change without notice. The MGE UPS SYSTEMS logo is a trademark of MGE UPS SYSTEMS.

Distributed by:
Power Sources Unlimited (website www.psui.com)
Telephone: (800)966-7784

Fax Number: (508)384-1896

Dimensions, weight and ref.

500

800

1100

1500

2200

Tower dimensions (HxWxD in inches)

5.9 x 9.3 x 16.3

5.9 x 9.3 x 19.0

Rack dimensions (HxWxD in inches)

1.73 (1U) x 17.2 x 13.9

1.73 (1U) x 17.2 x 19.6 1.73 (1U) x 17.2 x 20.6

3.5 (2U) x 17.2 x 25.2

Tower/Rack weights (in =lbs.)

– / 19.8

23.1/–

25.3/35.2

33/41.9

74.7

EXB module weight

92.3

Accessories supplied

removable and repositionable 19” rack-mount brackets, universal telescopic rails,

with Rack versions:

mounting hardware kit, rear attachment, cable lock system

Tower ref.

89341

89343

89345

Rack ref.

89340

89344

89346

Tower convertible to Rack ref.

89347

EXB module ref.

89350

MGE

UPS SYSTEMS

T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R

Characteristics

Battery charge level

Group of 6 outlets for
equipment connection with
2 programmable outlets

Power consumption

Complete user interface:
- on AC input / on battery
- booster/fader mode
- programmable outlet status
- battery replacement required

or UPS fault

Connection
of additional
battery modules

Slot for optional
communications
card

Data line

protection

Automatic recognition
of battery extensions

RS232 communications
port

USB communications
port

Repositionable
logo and battery
access plate

Pulsar
Evolution
2200

Advertising