Pulsar esprit specifications, Characteristics, Dimensions – MGE UPS Systems Pulsar Esprit 313.5 kVA User Manual

Page 6: Weights, Sizing guide, Battery runtimes

Advertising
background image

©MGE UPS SYSTEMS, Inc. All specifications subject to change without notice. The MGE UPS SYSTEMS logo is a trademark of MGE UPS SYSTEMS.

CANADA
#9, 2798 Thamesgate Dr.
Mississauga, ON L4T 4E8
tel (905)

672-0990

(877) 672-0990

fax (905) 672-7667

esprit 101
Effective: April 2000

USA (headquarters)
1660 Scenic Avenue
Costa Mesa, CA 92626
tel (800)

523-0142

(714) 557-1636

fax (714) 557-9788

www.mgeups.com
[email protected]

BRAZIL
Avenida Guido
Caloi 1985 (GALPAO 23)
Guarapiranga
Sao Paulo - SP, CEP 05802
tel (55)

11-5890-3323

fax (55) 11-5890-3353

ARGENTINA
Thames 91
1609 San Isidro
Prov de Buenos Aires
tel (54)

11-4766-8777

fax (55) 11-4766-6008

MGE

UPS

SYSTEMS

MGE GREEN SWEEP

Call MGE to return your UPS for free
recycling to a US EPA-certified recycling
center and help protect our environment.

Characteristics

Esprit 3.1

Esprit 4.5

Esprit 6

Esprit 9

❊❊

Independent test lab report available on MGE’s web site

Dimensions

and

Weights

Electrical
Power (VA/W)

3000/2016

4500/3150

6000/4032

8500/6000

Input voltage range

100/120/127 Volts +10% -15%

100/120/127 Volts +10% -15%

208/220/240 Volts+10%-15%

208/220/240 Volts+10%-15%

Output voltage range

100/120/127 Volts

100/120/127 Volts

100/120/127/200/208/220/240 Volts

Output frequency regulation

50/60 Hz +/- 0.5 Hz

Surge protection

420 joules

420 joules

630 joules

630 joules

Efficiency (on battery)

> 94%

> 94%

> 94%

> 94%

Waveform

Compatible with multiple server-grade, Power Factor Corrected (PFC) power supplies

❊❊

Batteries
Number and type

12 x 12V/7Ah

12 x 12V/7Ah

24 x 12V/7Ah

24 x 12V/7Ah

Recharge time

4 hours to 80%

4 hours to 80%

4 hours to 80%

4 hours to 80%

Battery life expectancy

4-5 years

4-5 years

4-5 years

4-5 years

User connections
Input power cord

6 feet w/ L5-30P

6 feet w/ 5-50P

6 feet w/ L14-30P

6 feet w/ 14-50P

Output receptacles

L5-30 & 4 x 5-15

5-50 & 4 x 5-15

L14-30, L6-30 & 6 x 5-15

14-50, L6-30 & 6 x 5-15

Communication ports

1xRS232 & 1xUSB

Software included

Solution-Pac Power Management suite

Environment
Safety

UL, cUL 1778

Surge protection

ANSI C62.41

Noise level

45 dBA max.

Operating temperature

32-105 F

Manufacturer certifications

FCC, ISO 9001

Warranty

2 years, parts and labor electronics (battery modules:1year)

Warranty extension (option)

3 years, parts and labor incl. batteries

Environmental

Recyclable components, packing & documentation, recycled materials, used battery recovery

3 PC

4 PC

5 PC

6 PC

2 RISC

9 PC

12 PC

15 PC

servers

servers

servers

servers

servers

servers

servers

servers

Esprit 3.1

17

Esprit 4.5

20

12

8

Esprit 6

45

26

18

15

13

Esprit 9

48

33

22

20

15

10

Esprit 13.5

100

70

55

47

40

25

18

13

Single UPS

Sizing Guide

and

Battery Runtimes

Single UPS

Power Cluster

(for servers with 2 redundant power supplies)

Model

Dimensions

Weight

Dimensions

Weight

WxHxD (in.)

(lbs.)

WxHxD (in.) each

(lbs.) each

Esprit 3.1

Electronic

1 ea. 8.5" x 7.25" x 19"

20

2 ea. 8.5" x 7.25" x 19"

20

Battery

1 ea. 8.5" x 7.25" x 19"

80

2 ea. 8.5" x 7.25" x 19"

80

Esprit 4.5

Electronic

1 ea. 8.5" x 7.25" x 19"

20

2 ea. 8.5" x 7.25" x 19”

20

Battery

1 ea. 8.5" x 7.25" x 19"

80

2 ea. 8.5" x 7.25" x 19"

80

Esprit 6

Electronic

1 ea. 17" x 7.25" x 19"

40

2 ea. 17" x 7.25" x 19"

40

Battery

2 ea. 8.5" x 7.25" x 19"

80

4 ea. 8.5" x 7.25" x 19"

80

Esprit 9

Electronic

1 ea. 17" x 7.25" x 19"

40

2 ea. 17" x 7.25" x 19"

40

Battery

2 ea. 8.5" x 7.25" x 19"

80

4 ea. 8.5" x 7.25" x 19"

80

Esprit 13.5

Electronic

3 ea. 8.5" x 7.25" x 19"

20

6 ea. 8.5" x 7.25" x 19"

20

Battery

3 ea. 8.5" x 7.25" x 19"

80

6 ea. 8.5" x 7.25" x 19"

80

3to1Interface

1 ea. 19” x 4” x 5.1”

20

2 ea. 19” x 4” x 5.1”

20

Esprit 13.5 consists of 3 each Esprit 4.5 plus 1 3 to 1 interface

Pulsar Esprit

Specifications

Esprit 4.5

Esprit 13.5
Power Cluster

Note: In a Power Cluster configuration, the battery runtimes given above will double.