MITSUBISHI ELECTRIC 9700 Series User Manual

Page 17

Advertising
background image

MITSUBISHI
ELECTRIC

9700 SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-10

MITSUBISHI ELECTRIC 9700 SERIES UPS

TABLE 1.4 Detail of Specifications

Rated Output kVA

100

150

225

300

375

Rated Output kW

80

120

180

270

338

AC INPUT CHARACTERISTICS

Configuration

3 phase, 3 wire

Voltage

208 V, 480 V, 600 V +10% ~ -15%

Input Power Factor

0.98 Typical

Frequency

60 Hz

±

5%

Reflected Current THD

3% max. at 100% load; 5% max. at 50% load

STATIC BYPASS INPUT

Configuration

3 phase, 3 or 4 wire

Voltage

120/208 V, 277/480 V, 346/ 600 V

±

10%

Frequency

60 Hz (

±

3% Tracking window)

BATTERY

Type

VRLA, Flooded Lead Acid, Nickel Cadmium

Ride Through

Application Specific

Nominal Voltage

360 VDC

Minimum Voltage

290 VDC

Number of Cells

176 ~ 185

AC OUTPUT

Configuration

3 phase, 3 or 4 wire

Voltage

120/208 V, 277/480 V, 346/ 600 V

Voltage Stability

±

1%

Frequency

60 Hz

Frequency Stability

±

0.01% in free running mode

Power Factor

0.8 nominal

0.9 nominal

Power Factor range

0.8 ~ 1.0 lagging (within output kW rating)

Voltage THD

2% maximum THD at 100% Linear Load
5% maximum THD at 100% non-linear load

Transient Response

±

2% maximum at 100% load step

±

1% maximum at loss or return of AC power

±

5% maximum at load transfer to/from static bypass

Transient Recovery

Less than 1 line cycle

Voltage Unbalance

1% maximum at 100% unbalanced load

Phase Displacement

1% maximum at 100% unbalanced load

Inverter Overload

125% for 10 minutes; 150% for 1 sec

System Overload

500% for 2 cycle (with bypass available)

Bypass Overload

125% for 10 minutes

Withstand Rating

65kA* *:with optional fuses

ENVIRONMENTAL

Cooling

Forced Air

Operating Temperature

2

°

F ~ 104

°

F (0

°

C ~ 40

°

C). Recommended 68

°

F ~ 86

°

F

(20

°

C ~ 30

°

C)

Relative Humidity

5% ~ 95% Non Condensing

Altitude

3300 Feet (1000 meters); 5000 feet @ 0.99 derating

Location

Indoor (free from corrosive gases and dust)

Paint Color

Munsell 5Y7/1 (Beige)

Advertising