Magnetic switch, Limit contacts. tattletale – Murphy Temperature SWICHGAGE A20 Series User Manual

Page 3

Advertising
background image

Bulletin AT-95026B page 3 of 4

Pre-Alarm Using A20/A25TABS

Typical Internal Wiring Diagrams

The A20TABS and A25TABS features a standard limit contact for equipment
shutdown on high temperature. It also has an internal SPDT snap-switch to sig-
nal an alarm before shutting down. When the snap-switch trips (preset point), on
rising temperature, the switch completes a circuit to activate an alarm. If the
temperature continues to increase, the face-adjustable pointer contact will make

and the shutdown circuit will be completed (see the typical diagram below for
reference). The front contact shutdown limit setting (which is adjustable) and
the snap-switch are preset at the factory. Refer to “Temperature Ranges and
Factory Settings” table on opposite page for settings. For alternative alarm
before shutdown, see Magnetic Switch model 760A or 761APH.

_

+

Battery

A20TABS

SWICHGAGE

®

Alarm Before

Shutdown

MINI-SIREN

®

Opens circuit to

shutdown engine.

Shutdown Device
or Ignition Circuit

518PH
TATTLETALE

®

HIGH

C

N. C.

N. O.

ABS

G

NC

R

SW1 SW2

B

Magnetic Switch

G

NC

R

SW1 SW2

B

_

+

Battery

A20P Pressure

SWICHGAGE

®

A20T Temperature

SWICHGAGE

®

518PH TATTLETALE

®

Energized To Run Devices

N.C. switches option

N.O. SWICHGAGE

®

instruments

C

LOW

N. C.

C

HIGH

N. O.

C

S

B

_

+

Battery

117 Magnetic Switch

Energized To Run Devices

A20T Temperature

SWICHGAGE

®

C

HIGH

N. O.

INDUCTIVE AND HIGH CURRENT LOADS REQUIRE THE USE OF A
MAGNETIC SWITCH.
The SWICHGAGE

®

contacts are for light-duty elec-

trical switching to operate alarms or control devices. Murphy manufactures the
Magnetic Switch for protection of the pilot-duty SWICHGAGE

®

limit contacts.

TATTLETALE

®

Magnetic Switches show the cause of shutdown for applica-

tions that include: capacitor discharge or magneto ignitions, battery systems and
electric motor driven equipment. Typical wiring diagrams are shown below.

C

HIGH

N. C.

N. O.

C

HIGH

N. C.

N. O.

LOW

HIGH

C

N. C.

N. O.

ABS

P

L

H

C

N. C.

N. O.

P

L

H

C

N. C.

N. O.

P

L

H

C

N. C.

N. O.

RESET

SET

HIGH

HIGH

HIGH

SET

RESET

SET

RESET

SET

RESET

LOW

HIGH

LOW

C

N. C.

N. O.

P

L

H

C

N. C.

N. O.

P

L

H

C

N. C.

N. O.

A20T

A20T-HL

A20TABS

A20TE

A25T

A25T-HL

A25TABS

A25TABS-HL

A25TE

Pointer shown in the shelf position. Pointer type contact rating: pilot-duty 2 A @ 30 VAC/VDC resistive.

Snap-acting switch rating: 3 A @ 30 VDC inductive. 4 A @ 125 VAC inductive.

Advertising