1. Confirming the Package Contents

The following items are included with the Twinning Kit (CMY-R100VBK, CMY-R200VBK). Verify that all items are present before
starting installation.

Always use the twinning pipes included in the kit when preparing the twinning kit.

If the pipes field-supplied do not fit the parts in the kit, use the accessory piping parts listed below.

(1) Package contents

Model

CMY-R100VBK

CMY-R200VBK

1

1

1

1

2

1

1

-

1

1

-

1

3

1

3

1

1

1

1

Low-pressure

twinning kit

2

High-pressure

twinning pipe

3

Fixing screw

4

Elbow pipe

Ø22.2 [7/8]

5

Elbow pipe

Ø28.58 [1-1/8]

6

Elbow pipe

Ø31.75 [1-1/4]

7

High-pressure pipe

(for routing through

the bottom)

8

High-pressure pipe

(for routing through

the front)

9

Pipe cover

Model

CMY-R100VBK

CMY-R200VBK

-

2

1

-

-

1

-

1

1

-

1

-

1

-

1

-

1

-

B

C

D

E

F

U-PIPE

ID25.4 [1]

G

U-PIPE

ID19.05 [3/4]
-ID25.4 [1]

H

Saddle

2

-

0

1

1

I

Packing

1

-

A

1

1

J

Fixing plate

2

2

K

Installation Manual

(this booklet)

L

Insulation cover

M

Cable tie

OD19.05 [3/4]
-ID15.88 [5/8]

OD22.2 [7/8]
-ID19.05 [3/4]

OD19.05 [3/4]
-ID22.2 [7/8]

OD22.2 [7/8]
-ID28.58 [1-1/8]

OD28.58 [1-1/8]
-ID22.2 [7/8]

OD31.75[1-1/4]
-ID34.93 [1-3/8]

(2) List of field-supplied parts

· Refrigerant pipes other than the ones provided in the kit
· Heat-resistant insulation material (for field-supplied refrigerant pipes)
· Insulation cover tape

Package unit name

Outdoor Twinning Kit

Component unit name

Outdoor unit 1

Outdoor unit 2

BC controller ~ Twinning pipe

High-pressure

Low-pressure

A

B

A0

B0

C0

D0

E0

F0

PURY-

Y(S)HM

PURY-

Y(S)HMU

PURY-

T(S)HMU

A0

P450

P500

P550

P600

P650

P700

P750

P800

EP400

EP450

EP500

EP550

EP600

P144

P168

P192

P216

P240

P144

P168

P192

P216

P240

B0

P250

P250

P300

P300

P350

P400

P400

P400

EP200

P250

EP300

EP300

EP300

P72

P96

P96

P120

P120

P72

P96

P96

P120

P120

C0

P200

P250

P250

P300

P300

P300

P350

P400

EP200

EP200

EP200

P250

EP300

P72

P72

P96

P96

P120

P72

P72

P96

P96

P120

D0

CMY-R100VBK

CMY-R200VBK

CMY-R100VBK

CMY-R100VBK

CMY-R100VBK

F0

Twinning pipe ~ Outdoor unit

Low-pressure

E or F

A3

B3

C3

D3

E3

PURY-

YHM

PURY-

YHMU

PURY-

THMU

A1

A2

A3

P200

Ш15.88

(

*

)

Ш19.05

(

*

)

EP200

Ш15.88

(

*

)

Ш19.05

(

*

)

P72

Ш15.88

(

*

)

Ш19.05

(

*

)

P72

Ш15.88

(

*

)

Ш19.05

(

*

)

B1

B2

B3

P250

Ш19.05

Ш22.2

EP300

Ш19.05

Ш22.2

P96

Ш19.05

Ш22.2

P96

Ш19.05

Ш22.2

C1

C2

C3

P300

Ш19.05

Ш22.2

(

*

A

)

-

-

-

P120

Ш19.05

Ш28.58

P120

Ш19.05

Ш28.58

D1

D2

D3

P350

Ш19.05

Ш28.58

-

-

-

-

-

-

-

-

-

E1

E2

E3

P400

Ш22.2

(

*

)

Ш28.58

-

-

-

-

-

-

-

-

-

-

Unit model

A1

B1

C1

D1

E1

High-pressure

C or D

A2

B2

C2

D2

E2

( Unit : mm [in] )

( Unit : mm [in] )

*

A : In case of CMY-R200VBK

Ø34.93

(

*

)

[1-3/8]

E0

Ш22.2

[7/8]

Ш22.2

[7/8]

Ш22.2

[7/8]

Ш22.2

[7/8]

Ш28.58

(

*

)

[1-1/8]

Ш28.58

[1-1/8]

Ш28.58

[1-1/8]

Ш28.58

[1-1/8]

Ш28.58

[1-1/8]

Ш28.58

(

*

)

[1-1/8]

Ш28.58

(

*

)

[1-1/8]

Ш28.58

(

*

)

[1-1/8]

Ш28.58

(

*

)

[1-1/8]

[5/8]

[3/4]

[5/8]

[3/4]

[5/8]

[3/4]

[5/8]

[3/4]

[3/4]

[7/8]

[3/4]

[7/8]

[3/4]

[7/8]

[3/4]

[7/8]

[3/4]

[7/8]

[3/4]

[1-1/8]

[3/4]

[1-1/8]

[3/4]

[1-1/8]

[7/8]

[1-1/8]

2. Selecting the Correct Size Refrigerant Pipes and Using the Twinning Kit

(1) Pipe size

1

Field-supply the pipes to be connected to the kit.

2

Choose the correct size pipe using the table below. Connect the field-

supplied pipe to the twinning kit for the sizes in the table that are marked
with an asterisk (*).

3

If the pipe was cut with a pipe cutter, remove the burrs and eliminate

foreign materials before connecting.

On the low-pressure side, the twinning kit connects to the pipes field-

supplied inside the outdoor unit.

The distributor on the low-pressure side must be placed in the outdoor unit

that has a larger capacity index of the two, regardless of the relative
positions of the outdoor units or their addresses.

If the distributor is placed in the outdoor unit that has a smaller capacity,

refrigerant will not be properly distributed and compressor failure may result.

( If outdoor units that have the same capacity are used in combination, the

distributor can be placed in either outdoor unit.)

Twinning pipe (high pressure)

Twinning Kit (low pressure)

C

E

D

A

B

To BC controller

To BC controller

Outdoor unit 2

Outdoor unit 1

F

2

See reverse.