Installing the grille, Fig. 9-11, Installing the intake grille (fig. 9-11) – MITSUBISHI ELECTRIC Mr. Slim PLA-A-AA User Manual

Page 17

Advertising
background image

17

9. Installing the grille

C

A

B

A Screw (4

× 8) 5

B Corner panel
C Safety wire

D

H

G

E

F

Fig. 9-11

Maintenance mode operation procedures

(1) Press the

TEST

button for three seconds to

activate the maintenance mode.

(2) Press the TEMP.

buttons to set the refrigerant address.

MAINTENANCE

(3) Select the data you want to display.

MENU

ON/OFF

Compressor
information

COMP ON
x10 HOURS

COMP ON
x100 TIMES

COMP ON
CURRENT (A)

Cumulative
operation time

ON/OFF
number

Operation
current

Display A

Display B

Display A

OUTDOOR UNIT
H·EXC. TEMP

OUTDOOR UNIT
OUTLET TEMP

OUTDOOR UNIT
OUTDOOR TEMP

Heat exchanger
temperature

Comp discharge
temperature

Outdoor ambient
temperature

Display A

Outdoor unit
information

INDOOR UNIT
INLET TEMP

INDOOR UNIT
H·EXC. TEMP

INDOOR UNIT
FILTER USE H

Indoor room
temperature

Heat exchanger
temperature

Filter operation
time

Display A

Indoor unit
information

* The filter operation time displayed is the number of hours the filter has been

used since the filter reset was performed.

(4) Press the

FILTER

button.

(5) The data is displayed in C.

(Airflow temperature display example)

Flashing

Waiting for
response

Approx.

10 sec.

147 °F

* Repeat steps (2) to (5) to check another date.

(6) Press the

TEST

button for three seconds or press the

ON/OFF

button to

deactivate the maintenance mode.

Stable operation
Using the maintenance mode, the operation frequency can be fixed and the op-
eration can be stabilized. If the air conditioner is stopped, use the following pro-
cedure to start this operation.

COOL
STABLE MODE

HEAT
STABLE MODE

STABLE MODE
CANCEL

Stable cooling
operation

Stable heating
operation

Stable operation
cancellation

Display A

Press the

MODE

button to select the operation mode.

Press the

FILTER

button.

Waiting for
stable operation

Display D

Stable
operation

10-20 min.

* You can check the data using steps (3) to (5) of the maintenance mode opera-

tion procedures while waiting for the stable operation.

10. Easy maintenance function [This function only for A-control]

By using the maintenance mode, you can display many types of maintenance data
on the remote controller such as the heat exchanger temperature and compressor
current consumption for the indoor and outdoor units.
This function can be used whether the air conditioner is operating or not.
During air conditioner operation, data can be checked during either normal operation
or maintenance mode stable operation.
* This function cannot be used during the test run.
* The availability of this function depends on the connecting outdoor unit. Refer to

the brochures.

D

A

C

B

Display example (Comp discharge temperature 147 °F)

Display C

9.8. Installing the intake grille (Fig. 9-11)

Note:
When reinstalling the corner panels (each with a safety wire attached), connect
the other end of each safety wire to the grille using a screw (4 pcs,
4

ЧЧЧЧЧ 8) as shown in the illustration.

* If the corner panels are not attached, they may fall off while the unit is operating.
• Perform the procedure that is described in “9.2. Preparing to attach the grille” in

reverse order to install the intake grille and the corner panel.

• Multiple units can be installed with grille so that the position of the logo on each

corner panel is consistent with the other units regardless of the orientation of the
intake grille. Align the logo on the panel according to the wishes of the customer as
shown in the diagram to the left. (The position of the grille can be changed.)

D Refrigerant piping of the main unit
E Drain piping of the main unit
F Position of the corner panel when sent from the factory (logo attached).

* Installation in any position is possible.

G Position of the levers on the intake grille when sent from the factory.

* Although the clips can be installed in any of four positions, the configuration shown here is

recommended.

(It is not necessary to remove the intake grille when maintenance is performed on the elec-
tric component box of the main unit.)

H Receiver (Only PLP-6AALM Panel)

BG79U795H01_en.pm6

05.12.1, 9:49 AM

17

Advertising