Advanced operations – MGE UPS Systems AmpMeter PDU User Manual

Page 39

Advertising
background image

4. Advanced Operations

Environmental Monitor Status traps

Status Error Description

Normal

The Environmental Monitor is working correctly

NoComm

x

Communication to the Environmental Monitor has been lost

Temperature/Humidity Sensor Status traps

Status Error Description

Found

The sensor has been detected

NotFound

No sensor has been detected

Lost

x

Sensor initially detected but communication to the sensor has been lost

NoComm

x

Communication to the sensor has been lost

NOTE: Traps are generated according to a hierarchical architecture; i.e. if a Tower Status enters a trap
condition, only the Tower Status trap is generated. Infeed and Outlet Status traps are suppressed until the
Tower Status returns to Normal.

Change trap

The Change trap is generated for all outlet status changes between any on/off conditions. Change traps
include the outlet status, Location of the AmpMeter PDU, and identifier and name of the affected outlet. For
descriptions of the outlet status types, please refer to the prior table.

Load Trap

The Load trap is generated whenever the total input load on an infeed exceeds a preset threshold. Load traps
include the reported input load, load status, Location of the AmpMeter PDU, and identifier and name of the
affected infeed.

Any error state generates a Load trap and triggers the trap timer. A new trap is generated at the end of every
timer period until the Load returns to a non-error status.

Load traps

Status Error Description

Normal

Infeed is on and within preset thresholds

NotOn

Infeed is off

Reading

Non-error state – Load status currently being read

LoadHigh

x

Infeed current load exceeds preset threshold

OverLoad

x

Infeed current load exceeds the measurable range for the infeed

ReadError

x

Unable to read Load status

NoComm

x

Communication to the infeed has been lost