7 dc injection brake (pr. 10 , pr. 11 , pr. 12 ), Caution – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 85

Advertising
background image

75

Explanation of functions (parameters)

2

F

UNCT

IO

NS

2.3.7

DC injection brake (Pr. 10

, Pr. 11

, Pr. 12

)

* The factory setting varies according to the inverter capacity. (Refer to the following table for details.)

<Setting>

•Use Pr. 10 to set the frequency at which the DC injection brake operation is started.

•Use Pr. 11 to set the period during when the brake is operated.

•Use Pr. 12 to set the percentage of the power supply voltage.

•Change the Pr. 12 setting to 4% when using the inverter-dedicated (constant-torque

motor).
(If the Pr. 12 value remains unchanged from the factory setting and Pr. 71 is changed
to the setting for use of the constant-torque motor, the Pr. 12 setting is automatically
changed to 4%.)

.

By setting the DC injection brake
voltage (torque), operation time
and operation starting frequency,
the stopping accuracy of
positioning operation, etc. or the
timing of operating the DC
injection brake to stop the motor
can be adjusted according to the
load.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

10

DC injection brake
operation frequency

3Hz

0 to 120Hz

Setting is enabled when
Pr. 30 = "1".
(When Pr. 11 is set to "0s" or
Pr. 12 is set to "0%", DC
injection brake is not
operated.)

11

DC injection brake
operation time

0.5s

0 to 10s

12

DC injection brake voltage

6%

0 to 15%

CAUTION

Install a mechanical brake. No holding torque is provided.

O

u

tpu

t f

re

quen

cy

(Hz

)

Time

Time

DC injection
brake voltage

"Operation
frequency"

Pr.10

Pr.12

"Operation
voltage"

Pr.11 "Operation time"