MITSUBISHI ELECTRIC FR-S520E User Manual

Page 89

Advertising
background image

79

Explanation of functions (parameters)

2

F

UNCT

IO

NS

2.3.12 Stall prevention function and current limit function

(Pr. 21

)

You can make setting to prevent stall caused by overcurrent and/or to prevent the
inverter from resulting in an overcurrent trip (to disable high-response current
restriction that limits the current) when an excessive current flows due to sudden
load fluctuation or ON-OFF on the output side of a running inverter.

• Stall prevention

If the current exceeds the stall prevention operation level (Pr.22), the output
frequency of the inverter is automatically varied to reduce the current.

• High response current limit

If the current exceeds the limit value, the output of the inverter is shut off to
prevent an overcurrent.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

21

Stall prevention
function selection

0

0 to 31, 100

Setting is enabled when Pr. 30 =
"1".

Pr. 21
Setting

High
Response
Current
Limit

:

Activated

: Not

activated

Stall
Prevention
Operation
Selection

:

Activated

: Not

activated

OL Signal
Output

:

Operation
continued

:

Operation
not
continued
(*)

Pr. 21
Setting

High
Response
Current
Limit

:

Activated

:Not

activated

Stall
Prevention
Operation
Selection

:

Activated

:Not

activated

OL Sig-
nal Out-
put

:

Opera-
tion con-
tinued

:

Opera-
tion not
contin-
ued(*)

A

ccel

era

ti

o

n

Cons

ta

nt

spe

e

d

D

ecel

era

ti

o

n

A

ccel

era

ti

o

n

Cons

ta

nt

spe

e

d

D

ecel

era

ti

o

n

0

16

1

17

2

18

3

19

4

20

5

21

6

22

7

23

8

24

9

25

10

26

11

27

12

28

13

29

14

30

15

31

* When "Operation not continued for OL signal

output" is selected, the "OLT" alarm code
(stopped by stall prevention) is displayed and
operation stopped.

(Alarm stop display "

")

10

0

Dr

iv

in

g

R

egene

ra

tiv

e

Advertising
This manual is related to the following products: