Horizontal Vent Installation

IMPORTANT NOTES:

1. All Ravelle™ 42 gas fireplaces horizontally terminated vent

installations use 8”x 5” Security™ Secure Vent™ or Simpson

Dura-Vent GS direct-vent pipe.

2. When this pipe passes through a wall, a wall thimble - Security

#SV5RSM or Simpson #1247 is required. The hole in the wall

for the wall thimble should be 10-3/4” x 10-3/4”.

3. Horizontal runs of vent must be supported every three feet.

Wall straps - Security #SV5BM or Simpson #1288 are available

for this purpose.

4. If the vent passes through a ceiling or floor, a firestop - Security

#SV5BF or Simpson #1263 is required.

5. Venting terminals shall not be recessed into a wall or siding.

If installing the termination cap on a wall covered with siding,

a vinyl siding standoff - Security #SV5VS or Simpson #1250

or furring strips must be used to ensure that the termination

cap is not recessed into the siding.

6. The horizontal run of vent must have a 1/4” (6mm) rise for

every 12” (305mm) of run towards the termination.

7. If the wall being penetrated is constructed of non-combus-

tible material, such as masonry block or concrete, an 8-1/2”

(216mm) diameter hole is acceptable and a wall thimble is

not required.

8. The location of the horizontal vent termination on an exterior

wall must meet all local and national building codes and must

not be blocked or obstructed. For allowable external vent

terminations locations, see the diagram on Page 20.

9. Allowable clearances from the vent pipe to combustible materi-

als must be maintained. See Page 7 for these clearances.

10. Do not locate the termination cap where it may be blocked by

shrubbery or snow.

Vertical Vent Installation

IMPORTANT NOTES:

1. All Ravelle 42 gas fireplace vertically terminated vent installations

use 6-5/8” x 4” Security or Simpson Dura-Vent GS direct-vent

pipe.

2. Fireplaces that are vertically terminated require pipe reducer

- Lennox Hearth Products #75247 - installed on the fireplace’s

flue collar before the

direct-vent pipe can be installed.

3. If the vent passes through a ceiling or floor, a firestop - Security

#SV4BF or Simpson #963,

4. If the vent passes through the roof, a roof flashing - Security

#SV4FA or SV4FB, Simpson #943 or 943S and storm collar

- Security #SV4FC, Simpson #953 are required.

5. Allowable clearances from the vent pipe to combustible materi-

als must be maintained. See Page 7 for these clearances.

6. A maximum of two 45º elbows may be used. See Page 19 for

allowable offsets.

7. The maximum system height is 30 feet (9.1 M) and the minimum

is 10 feet (3 M).

Note:

Verify that you have

at least the mini-

mum clearance to

combustibles at the

roofline.

Flashing

Simpson

(Part # 943 or 943S)

Secuirty

(Part #SV4FA or SV4FB)

Vertical Termination Cap

Security (Part #SV4CGV)

Simpson (Part # 980)

Pipe

Length

Ceiling Firestop

Simpson (Part # 963)

Security (Part # SV4BF)

Ceiling Minimum

Framing 10” x 10”

(254mm x 254mm)

Storm Collar

Simpson (Part # 953)

Security (Part #SV4FC)

Roof- Maintain 1”

(25mm) Clearance

to Combustibles

Figure 19

10-3/4”x 10-3/4”

(273mm x 273mm)

Framed Hole

Termination Cap

Wall Thimble

Elbow