5.THE COMMERCIAL POWER SUPPLY-INVERTER SWITCH-OVER SEQUENCE FUNCTION

If the commercial power supply-inverter switch-over sequence function is activated with the FR-A5AR mounted on
the inverter, the phenomenon where magnet contactor switches alternate between ON and OFF may occur.
To prevent this, adapt either connection shown below.
(1) Recommended connection example 1

Use inverter output terminals (Contact sig-
nal, open collector signal) instead of MG1
signals.
The phenomenon occurs when relay out-
put of the FR-A5AR is used as MC1 signal.

(2) Recommended connection example 2

When using relay output of the FR-A5AR,
set the alarm output signal (ABC) instead
of the MC1 signal and output it from con-
tacts B and C.

CAUTION

For the FR-V500 series, the commercial power supply-inverter switch-over sequence function can not be used.

IM

NFB

S1

R1

T

S

R

MC1

MC2

W

V

U

MC3

MC1

MC1

open collector

or

contacts
A and C

MC2

MC3

FR-A5AR

A
C

Supply

Motor

Inverter

MC2

A
C

MC3

IM

NFB

S1

R1

T

S

R

MC1

MC2

W

V

U

MC3

ABC

MC1

FR-A5AR

Supply

Motor

Inverter

MC2

C

MC2

MC3

A
C

MC3

B

A
C