Example of safety system configuration, Example 1, Attention – MITSUBISHI ELECTRIC FR-D700 User Manual

Page 7

Advertising
background image

5

3. Example of safety system configuration

Example 1























Fig.3 Safety system example 1 – STOP asynchronous with EM and fault detection through A-C output.


For safety stop, configure the wiring as shown in Fig.3 above.
Note: the above wiring is configured to prevent restart in case of a fault.

The parameter No.192 must be set to ‘199’. This setting makes the A-C output to open in case of failure.

After the power-up, to reset the safety stop mode, press the START switch, and also press the STF switch,
then start the motor rotation.

In the above configuration, after reset of EM switch, drive will be in safe-state until START switch is
pressed.

ATTENTION

To prevent restart in case of recovering from input power loss of drive, 3-wired connection for STF/STOP
control is recommended.
In case of 2-wire connection and using latching type switch to short between STF and SD/PC for starting,
ensure the compliance with safety requirement for the restarting when the drive recover from input power
loss.

S2

S1

SC

FR-D700

START

+24V

EM

QS90SR2SN-Q

K1

A

CPU

X0

X1

COM0

COM1

24G

Safety

Logic

Circuit

XS0

XS1

Z10

Z00

Z20

Z11

Z01

Z21

K2

DC24V

RY

B
C

R S T

U V W

MITSUBISHI MELSEC Safety relay unit

Gate

Driver

Gate

Driver

IGBTs

IM

STF

PC

SOURCE

STOP

STOP

STF

Advertising