MITSUBISHI ELECTRIC MXZ-32SV User Manual

Page 21

Advertising
background image

21

(1) LEV opening correction by suction super heat (COOL, DRY)

(Suction super heat) = (Minimum gas pipe temperature) - (Evaporation temperature)
When COOL and DRY , correct the LEV openings corrected from the table below

(2) Separate correction (COOL,DRY)

(When number of operation unit is 2 units or more)
(a) Correction by the separate super heat

Correct the LEV separately by temperature difference between each gas pipe temperature thermistor and evaporator
temperature thermistor.

1

Calculate each super heat of the unit from the expression below;

(Super heat) = (Gas pipe temperature thermistor) - (Evaporation temperature thermistor)

2

Select a minimum super heat from among them.

3

Correct an each LEV is corrected opening is corrected by difference between each super heat and minimum super

heat.

1

Suction super heat

(MIN gas pipe temperature thermistor - Evaporation temperature thermistor)

2

Each correction

w

1

• (Each gas pipe temperature thermistor - Evaporation temperature thermistor)
• (Main pipe temperature thermistor - sub pipe temperature thermistor)

w

1 Perform this, when number of operation units is 2units or more

w

2 When the correction opening of suction super heat is 0, correct the LEV opening by dischaege temperature.

3

Discharge temperature

COOL

DRY

HEAT

-

w

2

w

2

<Correction>

OB254-1.qxp 03.1.16 4:33 PM Page 21