One thermocouple only, Open thermocouple input, Mdtm89 wiring and adjustment instructions – Murphy Dual Temperature SWICHGAGE MDTM89 User Manual

Page 2

Advertising
background image

MDTM-8907N page 2 of 4

One Thermocouple Only

Even though the MDTM89 is a dual temperature monitor, it will monitor
and display one temperature with equal results.

When monitoring one temperature, always jumper the unused thermocou-
ple terminals on the back of the MDTM89 with a short length of wire.
The unused channel will display approximate ambient temperature.

Open Thermocouple Input

An open thermocouple input forces the monitor into upscale overrange.
The monitor indicates an overrange by displaying the numeral “1” in the
left most digit of the display. An overrange will turn on the trip point out-
put, for the respective thermocouple.

MDTM89 Wiring and Adjustment
Instructions

A. Using Thermocouple Extension Wire

1. After thermocouple installation, connect the thermocouple leads to

the MDTM89 according to the instructions.

IMPORTANT: Use correct wire for the thermocouple selected.
USE ONLY THERMOCOUPLE EXTENSION WIRE.

2. If the thermocouple leads are not long enough you will need to use

shielded thermocouple extension wire. The thermocouple extension
wires, from your thermocouple lead wires to the terminals of the
MDTM89, must be of the same material as the thermocouple lead
wires. (See Table 1.)

4-3/4 in.

(121 mm)

120

2-39/64 in. radius

(66 mm)

1/4 in.
(6 mm)
typical
diameter

120

4-3/4 in.

(121 mm)

4-1/4 in.

(108 mm)

4 in.

(102 mm)

5-1/2 in.

(140 mm)

TC1

TC2

Screw for

Equipment Ground

Remove Jumper(s)

to Install

Thermocouple

Mount the MDTM89 temperature SWICHGAGE

®

in a place where it

will be protected from rain and splashing water. A minimum distance of
12 in. (305 mm) from any ignition coils or coil leads should be main-
tained. The MDTM89 flush mount case is intended for mounting in a flat
panel .032 in. (1 mm) to .125 in. (3 mm) thick.

First, cut a 4-

3

/

4

in. (121 mm) diameter hole and three

1

/

4

in. (6 mm)

diameter fastening holes as shown below. Insert the SWICHGAGE

®

from the back side of the panel. Using the three 10-24 screws, included
with the SWICHGAGE

®

, secure to the panel.

Mounting Hole Pattern

J

Jx

White/Iron

Red/Constantan

K

Kx

Yellow/Chromel

Red/Alumel

Table 1. Thermocouple Extension Wire Color Code

Thermocouple

Type

Thermocouple

Extension Wire

Color Code/Material

Positive Lead

Negative Lead

14

.07

.146

16

.137

.230

18

.222

.374

20

.357

.586

24

.878

1.490

Table 2. Thermocouple Extension Wire Loop

Resistance in Ohms per Foot at 68°F

Size

AWG No.

Type “J”

Type “K”

Thermocouple lead length: 150 ohm lead resis-
tance affects monitor accuracy less than 1°.

Back View

Side View

Front View

MOUNTING DIMENSIONS

WIRING AND ADJUSTMENT INFORMATION

CAUTION:

Perform the wiring operation with the power source “OFF”. Make sure the voltage and current requirements are

within the SWICHGAGE

®

ratings. Keep all high voltage wiring, such as spark plug wires away from THERMOCOUPLES

AND EXTENSION WIRING. Before wiring determine the voltage and polarity for the application.