Appendices, Comet series 11 general characteristics, Cont') – MGE UPS Systems Comet TM 5 - 30 kVA User Manual

Page 50

Advertising
background image

Comet installation and user manual: E-6761200XT/FB

11.2

Merlin Gerin by MGE UPS SYSTEMS

Comet series 11 general characteristics

apparent power (kVA):

5

7.5

10

active power (kW):

4

6

8

efficiency (%):

91

91

91

heat losses (W):

445

668

890

noise level (dBa):

on RL load:

45

46

46

on RCD load:

50

53

53

battery backup time (minutes):

at rated load (power factor 0.6):

8

10

10

maximum leakage current (mA):

directly earthed neutral system (TT):

10

23

23

during a fault with an impedent neutral system: 28

60

60

dimensions and weight

height (mm):

730

910

910

width (mm):

360

400

400

depth (mm):

420

550

550

weight (kg):

90

190

210

AC input

number of phases:

1

voltage (V):

187 to 257

frequency (Hz):

47 to 63

power factor:

> 0.99

current distortion (%):

< 5

< 3

< 3

inrush current:

< In

AC output

number of phases:

1

voltage (V):

220 / 230 / 240

voltage tolerance (%):

±

1

frequency (Hz):

50 / 60

frequency tolerance (free-running) (%):

±

0.1

frequency tolerance (synchronized) (%):

±

1 /

±

1.5 /

±

2 /

±

3 /

±

4

synchronization rate (Hz/s):

1 / 2

appendices

(cont')