Utside, Ombustion, Recautions – Martin Fireplaces SB5400SS User Manual

Page 22: Ecommendations

Advertising
background image

O

UTSIDE

C

OMBUSTION

A

IR

P

RECAUTIONS

& R

ECOMMENDATIONS

21

CONCRETE SLAB INSTALLATION
(OPTIONAL OUTSIDE AIR RUNS)

INLET GRILLE
IN SOFFIT
(OVERHANG)

8' MAX.

FIRESTOP SPACER

CAUTION: DO NOT TAKE
COMBUSTION AIR FROM
ATTIC SPACE OR GARAGE.

TERMINATION CAP

INSTALLATION ABOVE BASEMENT

INSTALLATION ABOVE BASEMENT
OR CRAWL SPACE

OR CRAWL SPACE

FIRESTOP SPACER

TO OUTSIDE WALL

DUCT EXTENDED
TO MISS JOIST

SECOND FLOOR

LONGER LENGTH OF THE TUBE
TO OUTSIDE.

INSULATION RING

INSERT SHORTEST SIDE
OF THE TUBE THROUGH
THE FIREPLACE OUTER
WRAP TO PROPERLY
SEAL AGAINST FIREBOX
WALL AND GASKET.

STEP 1: SECURE OUTSIDE AIR STARTING
COLLAR TO LEFT SIDE OF FIREPLACE WITH
FOUR SHEET METAL SCREWS PROVIDED.

NOTE: THE STARTING COLLAR EXTENDS
THROUGH THE OUTER FIREPLACE JACKET
AND WILL SEAL AGAINST THE FIREBOX
WALL WHEN SECURED AS INDICATED.

SECURING OUTSIDE AIR STARTING COLLAR TO FIREPLACE

STEP 2: SECURE OUTSIDE
DUCT TO STARTING COLLAR
WITH DUCT CLAMP OR SCREWS.

AK4 COMBUSTION
AIR KIT (SHORTEST
TOWARD FIREBOX)

AK4 MOUNTING PLATE

FIREBOX INSULATION SEAL

FIREPLACE OUTER WRAP

N

OTE

: The use of outside air for combustion is optional unless required by building codes. It is only necessary

to supply outside combustion air to one side of the fireplace. Use the model AK4 combustion air kit.

F

IGURE

23

53D9028. Rev 1 03/03