518aph, 518e, 520aph – Murphy M-6797B User Manual

Page 3: 521ph, 822ph, M4264 series, R129a, Ets30s, 518ph, Ms2111

Advertising
background image

M-6797B page 3 of 4

518APH

Allows for SWICHGAGE

®

and/or

N.C. contacts to be wired “Closed Loop” (in
series). Any contact open or SWICHGAGE

®

contact close in the circuit shunt trips the
518APH. Specify 12 or 24 VDC. Contacts 10
amps 24V. 14 amp fuse.

518E

Same as 518APH but recommended

for high vibration application where nuisance
shutdowns typically occur due to higher than
normal vibrations (ie. wood chippers) 12 Volt

only.

R

G NO

NC

SW1

SW2 B

520APH

Same as 518APH except with 30

second time delay before trip on one SWICH-
GAGE

®

contact input but immediate trip on the

second SWICHGAGE

®

contact input. Typical

use is for immediate stop of engine from oil
pressure or coolant temperature, but delayed
shutdown from alignment switches on center
pivot irrigation system. Specify 12 or 24 VDC
and length of time delay. Time delays are
available from 5 to 120 seconds. Contacts 10 amps
24 V. 14 amp fuse.

R

G NO

NC

SW1

SW2 B

TD

521PH

Use with N.C. SWICHGAGE

®

or

switches to ground magneto or CD ignition
when tripped. Trip coil energized to run, de-
energized to shutdown when N.C.
contacts open. Specify 12 or 24
VDC. Contacts 10 amps 24 V.

G

SW

NC

C

822PH

Used in Murphy TR-assemblies as

master disconnect. 24 VAC coil energizes
when SWICHGAGE

®

contact closes to

ground; breaks and makes circuit when
tripped. Manual reset.

NO

NC

C

SW

M4264 Series

Detects loss of

magneto/CD ignition output and transfers con-
tacts for customer use. Contacts 10 amps; 48
VAC/VDC.
M42641CD transfers SPDT dry contacts when
tripped.

760A/760AF/761APH

Use for distribu-

tor ignition or diesel. Time delay lockout of
SWICHGAGE

®

contacts on start-up only; cus-

tomer wired for delayed or immediate trip on
shutdown. Breaks and makes circuits when
tripped. 760A resets automatically when the
shutdown signal is removed or power is
removed. 761APH has manual reset. 760AF is
760A with inline fuse. Must specify 12 or 24 VDC, and length
of time delay. Optional time delays: 15, 30 (standard) or 60
seconds. Contacts 10 amps 24 V. 14 amp fuse. Models 760A
and 761APH carry the CE mark.

G

NO

NC

B

S

TD

IGN

NO

C

BY

NC

IGN

Sensing

Circuit

R129A

A SPDT relay with 10 amp dry

contacts. Specify 12 or 24 VDC. Contacts 10
amps 24 VDC. 14 amp fuse.

NO

NC

S

B

G

ETS30S

All solid-state time delay for energized to stop circuits such as

solenoids. When a shutdown signal is received, the ETS30S applies power to
the shutdown device for 30 seconds and then disconnects the power. Input
power 12 or 24 VDC.

518PH

Aallows for SWICHGAGE

®

and/or

N.C. contacts to be wired “Closed Loop” (in
series). Any contact open or SWICHGAGE

®

contact close in the circuit shunt trips the
518PH. Specify 12 or 24 VDC. Contacts 10
amps 24V. 14 amp fuse.

R

G

NC

SW1

SW2 B

* Complies with EMC Council directive 89/336/EEC regarding electromagnetic compatibility.

*

*

MS2111

Replaces 221PH w/72 ohm coil.

Used with NICS-78 non-incendive control
system. Service part only.

6

2

3

5

1

4

*

Advertising