4. troubleshooting check table – MITSUBISHI ELECTRIC MSZ-FA35VA User Manual

Page 18

Advertising
background image

18

NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first

detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with
OPERATION INDICATOR lamp flashing.

No.

1

3

5

6

Symptom

Operation indicator lamp

Detection method

Check point

POWER lamp flashes.
0.5-second ON

0.5-second OFF

Mis-Wiring
or serial
signal

Outdoor
power
system

Outdoor
thermistors

Outdoor
control
system

Indoor coil
thermistor

When the serial signal form the outdoor unit is
not received for a maximum of 6 minutes.

When it consecutively occurs 3 times that the
compressor stops for overcurrent protection or
start-up failure protection witth in 1 minute
after start-up.

When the outdoor thermistors short or open
circuit during the compressor operation.

When it cannot properly read data in the
nonvolatile memory of the inverter P.C. board
or the outdoor electronic control P.C. board.

• Refer to "Check of outdoor

thermistor".

Refer to service manual
OB372 or OB377.

• Refer to "Check of inverter/

compressor".

Refer to service manual
OB372 or OB377.
Check the stop valve.

• Replace the inverter P.C.

board or the outdoor

electronic control P.C. board.

Refer to service manual

OB372 or OB377.

• Refer to 9-6.

D

"How to check

mis-wiring and serial signal

error".

4

Indoor fan
motor

7

Abnormal

point

Outdoor unit
does not
operate.

Room
tempera-
ture
thermistor

POWER lamp flashes.
2-time flash

2.5-second OFF

When the indoor coil or the room temperature
thermistor is short or open circuit.

• Refer to 9-7.the
characteristics of indoor coil
thermistor, and the room
temperature thermistor.

POWER lamp flashes.
3-time flash

2.5-second OFF

When the rotational frequency feedback
signal is not emit during the indoor fan
operation.

• Refer to 9-7.

A

"Check of

indoor fan motor".

Indoor unit
and outdoor
unit do not
operate.

POWER lamp flashes.
5-time flash

2.5-second OFF

POWER lamp flashes.
6-time flash

2.5-second OFF

Indoor unit
and outdoor
unit do not
operate.

Indoor unit
and outdoor
unit do not
operate.

Indoor unit
and outdoor
unit do not
operate.

Other
abnonmality

An abnormality other than above mentioned is
deteced.

• Confirm the abnormarity in
detail using the failure mode
recall function.

Indoor unit
and outdoor
unit do not
operate.

Indoor unit
and outdoor
unit do not
operate.

8

Outdoor
control
system

When it cannot properly read data in the
nonvolatile memory of the inverter P.C. board
or the outdoor electronic control P.C. board.

• Check the blinking pattern of
the LED on the inverter P.C.
board or the outdoor lectronic
control P.C. board.

2

Outdoor unit
does not
operate.

POWER lamp flashes.
7-time flash

2.5-second OFF

POWER lamp flashes.
14-time flash

2.5-second OFF

POWER lamp lights up

9-4. Troubleshooting check table

NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting.

Self check table

Lighted

Blinking

Not lighted

· Flashing of POWER lamp indicates abnormalities.

OB371_--1qxp 05.1.17 12:50 Page 18