Standard enclosure dimensions (all models), Ifications, Asm3000 controller spec – Murphy Generator Control System MGC2000 User Manual

Page 2: C• relative humidity: 95% @ 60

Advertising
background image

Power supply:

• Continuous voltage range: 8-35 VDC
• Brown out voltage < 5 VDC for 2 secs (recovery to 8V)
• Blackout voltage: 0V for 50mS (from 10V, recovery to 5V)
• Overvoltage withstand: 50 VDC for 5 seconds (to SAEJ1810 load

dump immunity

• Reverse voltage withstand: 100 VDC continuous
Current consumption (standby): 50mA
Current consumption (max): 500mA (plus output loads)

DC Inputs:

• Pressure, coolant temperature
• Closed to negative DC (±3V) on fault auxiliary and charger faults
• Remote start positive open from positive DC to start
• Remote start negative close to negative DC (±3V) to start.

AC Inputs:

• Magnetic pickup: 3 – 60 VAC, 50Hz – 10 kHz.
• Generator AC: 600 VAC max (L-L or L-N), 50/60 Hz.

Outputs:

• Fuel: positive DC (FET switched), 5A max.
• Crank, preheat: positive DC (FET switched), 2A max.
• Common alarm, fault lockout negative DC (semiconductor), 300mA max.
• Generator Hz. meter: 0 – 1 mADC (@ 45–65Hz).

Physical:

• Operating temperature: -10 to +65

o

C

• Relative humidity: 95% @ 60

o

C

• Environmental protection: AS3000U front: IP65, NEMA4

Vibration: ISO 88528 pt.9, & 3 axis 3g

Standard terminal blocks inside the MGC2000 enclosure. Booted type

grommets for a tight seal are available.

MGC-02029B page 2 of 4

16-80 in. (427 mm)

16-80 in. (427 mm)

9.25 in. (235 mm)

7.94 in.

(202 mm)

6.81 in.

(173 mm)

kPa

PSI

50

75

100

0

0

25

350

700

kPa

PSI

50

75

100

0

0

25

350

700

QUARTZ

HOURS

kPa

PSI

50

75

100

0

0

25

350

700

OFF/

STOP

REMOTE START
DEMAND

OVERCRANK

ENGINE RUNNING

LOW OIL
PRESSURE

BATTERY
CHARGER FAIL

A-C

VOLTS

A-C

AMPERES

HERTZ

HIGH ENGINE
TEMPERATURE

PLANT FAIL/
AUXILIARY INPUT

OVERSPEED

MANUAL

START

AUTO

START

OFF

3

1

Hinges for front-opening door option shown in shaded areas.

Mounting Pattern

Front View

Side View

Bottom View

6.36 in.

(162 mm)

9.25 in.

(235 mm)

Standard Enclosure Dimensions (all Models)

ASM3000 Controller Spec

ifications

WARNING: Do not bundle AC and DC wiring together. It is required
to use separate conduit runs and keep apart by at least 2 inches.