MGE UPS SYSTEMS

Pulsar EX: E-51032233XT/AC

13

communication

c

the U-Talk communication port, at the rear

of the Pulsar, delivers information in the
form of an RS232 series link supported by
the communication protocol exclusive to
MGE UPS SYSTEMS.
The Solution-Pac

TM

programs use the data

made available by this protocol.

option 2

c

SNMP card: after the card is installed in

the rear of the Pulsar, the communication
port transmits information supported by the
SNMP protocol on an RJ45 or BNC
connector.

Contact your sales agent for further details.

option 1

c

status information card: after the card is

installed in the rear of the Pulsar,
communication port transmits the status
information on a SUB-D 9-pin female
connector using the following pinouts:

1 - ground,
4 - normal operation,
5 - common,
6 - operation on utility power,
7 - low battery warning,
8 - load supplied by UPS,
9 - operation on battery.

optional port

12

5

4

3

2

1

9

8

7

6

0V

0V

n.o.

n.c.

0V

n.o.

0V

n.o.

0V

n.o.

Relay breaking capacity:
Vmax = 25V DC
Imax = 10mA

n.o. : normally open,
n.c. : normally closed.

With the EX Driver software program you
can set up Pulsar EX to suit your user
conditions (EX Tuner), supervise your UPS
and safeguard your system (UPS Manager
3.1). To install EX Driver, connect the serial
cable supplied to COM1 to COM4 (set up by
EX Tuner) series port of your computer
equipped with Windows 3.1 on the one end,
and to the serial Pulsar EX connector on the
other end. Insert the disk and type A:\Install.
Follow the installation instructions on the
screen. You may then use 2 software
programs :

v

EX Tuner to set up Pulsar EX,

v

UPS Manager 3.1 to supervise and

safeguard your system.

11

5

4

3

2

1

9

8

7

6

0V

RD TD

standard port

Advertising