Model EA150

Automatic Engine Controller with
Built-in SWICHGAGE

®

Instruments

And Hourmeter

Quick and Easy to Install

Advanced, Rugged, Reliable
Microprocessor Based Design

Very Competitive Low Cost

Operates On 12 or 24 Volt Systems

First-out Shutdown LED

Description

The EA150 Automatic Engine Controller
provides you with simple–yet sophisticated,
engine automation. It features basic auto-
matic start/stop capabilities plus other fea-
tures found on more sophisticated and
expensive controllers–all in an easy to
install panel.
The EA150 operates from 12 or 24 volt sys-
tems. It includes crank and rest cycles, sens-
ing circuit for crank disconnect and over-
speed, overcrank, and re-crank on false starts.
Four LEDs indicate first-out shutdown for:
low pressure, high temperature, overcrank
and overspeed. A fifth LED for engine run-
ning indicates when crank disconnect occurs.
The built-in oil pressure and water tempera-
ture SWICHGAGE

®

instruments provide visu-

al indication and can be set to initiate shut-
down on critical pressure and temperature.
The electromechanical quartz base hourme-
ter can record up to 9,999.9 hours. It is
housed in a shockproof case and built to be
rugged and durable for a long life.
A selector switch allows you to manually
select the operation sequence.

Features

Compact Design

Adjustable Overspeed circuit

Adjustable Overcrank circuit

Adjustable Shutdown Lockout Delay

Adjustable Crank Disconnect Setpoint

Engine Running Indication LED

Re-Cranks Engine on False Starts

Advanced Microprocessor Technology

Offers Reliability, Small Size, and Low Cost

Convenient Hat Bracket design for simple
engine mounting

Built-in Hourmeter

Temperature SWICHGAGE

®

Oil Pressure SWICHGAGE

®

Operates On 12 or 24 volt systems

Specifications

Power Input

12 or 24 VDC.

Operating Temperature

-40 to 185°F (-40 to +85°C).

Outputs

5 A relay for cranking and fuel valve.

300 mA transistor for engine annunciation.

Cycle Crank Timer

Up to 8 attempts. Re-Cranks on false
starts (fixed 30 seconds).

Crank/Rest Cycle Timing

4 to 25 seconds (adjustable).

Shutdown Time Delay

1 to 25 seconds (adjustable). Locks out
low oil and high temperature on start-up.

Crank Disconnect Speed Setting

From 30 to 8500 Hz.

Overspeed Trip Point Setting

From 30 to 8500 Hz.

Magnetic Pickup Input

Requires 2V rms minimum.

Shipping Weight

5 lbs. 4 ozs. (2.38 kgs.).

Shipping Dimensions

9-3/4 x 9-1/2 x 6 in. (248 x 241 x 152 mm).

EA-94013B

Revised 09-96

Catalog Section 30

(00-02-0083)