17

6.2 Voltage Drop of Extension Cable
Since 5VDC is supplied to the QA6ADP from the power supply module mounted
on the main base unit, the voltage drop will be caused in the extension cable.
If the specified voltage (4.75VDC or more) is not supplied to the IN side
connector of the QA6ADP+A5 B/A6 B, wrong input/output may occur.
When using the QA6ADP, check that the IN side connector of the
QA6ADP+A5 B/A6 B has 4.75VDC or more.
The following shows an example regarding how to calculate the voltage drop.

Model

Conductor

resistance value

QC05B 0.044
QC06B 0.051
QC12B 0.082
QC30B 0.172
QC50B 0.273

QC100B

0.530

I2

IA

IA

R1

V1

R2

V2

R3

V3

First extension stage

Second extension stage

Third extension stage

Main base unit

Extension base unit (QA6 B)

Extension base unit (A5 B)

Extension base unit (A6 B)

Power

supply

module

Power

supply

module

Power

supply

module

I3

I1

Symbol Description

V

Sum of voltage drop

V1

Voltage drop due to an extension cable between the main base unit and
the QA6 B

Vn

Voltage drop due to an extension cable between the extension base unit
(n-1th extension stage) and the extension base unit (nth extension stage)

R1

Resistance value of a cable between the main base unit and the
extension base unit QA6 B

Rn

Resistance value of an extension cable between the extension base unit
(n-1th extension stage) and the extension base unit (nth extension stage)

I1 to I3 5VDC current consumption in the first to third stages *1

IA

Current consumption of the QA6ADP

*1: Since the current consumptions I1 to I3 vary depending on modules to be

mounted, refer to the manual for the module to be mounted.

V V1 V2 V3 R1 ( I2 IA 2 ) R2 ( I2 IA 2 ) R3 IA

[Calculating formula]

The minimum value of the 5VDC output voltage of the power supply module
mounted on the main base unit is set to 4.90VDC. Therefore, the voltage of the
IN side connector of the QA6ADP+A5 B/A6 B in the final stage is 4.75VDC or
more only when the sum (V) of voltage drop is 0.15V or less.