5

Positioning the Uninterruptible Power Supply

32–55 kg

(70–120 lb)

Attention: The uninterruptible power supply will remain heavy without the battery modules. Select a location
sturdy enough to handle the weight.

Do not operate the uninterruptible power supply in excessive dust or in temperature and humidity conditions outside the speci-
fied limits.

Make sure that the air vents on the front and rear of the uninterruptible power supply are not blocked.

Placement of the unit should correspond with the following graphical depiction.

Hardwiring the Uninterruptible Power Supply

Attention: Wiring must be performed by a qualified electrician.

1. Install a utility circuit breaker according to local electrical codes (see tables below) for input wiring.

200/208 V Applications

Input Connection

Output Connection (Optional)

Single-Phase: Wire to L1, N, and

.

Wire to L1A, N1, and

.

System Wiring

Voltage

Current
Full Load
(Nominal)

External
Circuit Breaker
(typical)

Wire Size
(typical)

Input

200/208 V

38 amps

50 amps / 2-pole

10 mm

2

UPS 7500XHV

Output

200/208 V

38 amps

(as needed)

10 mm

2

Input

200/208 V

50 amps

63 or 70 amps / 2-
pole

16 mm

2

UPS 10000XHV

Output

200/208 V

50 amps

(as needed)

16 mm

2

220/230/240 V Applications

Input Connection

Output Connection (Optional)

Single-Phase: Wire to L1, N, and

.

Three-Phase: Wire to L1, L2, L3, N, and

.

Wire to L1A, N1, and

.

System Wiring

Number
of
Phases

Voltage Current

Full Load
(Nominal)

External
Circuit Breaker
(typical)

Wire Size
(typical)

Input

1

220/230/240 V

38 amps

50 amps / 2-pole

10 mm

2

Input

3

380/400/415 V

14 amps/
phase when online,
38 amps on L1 in
bypass

50 amps/ 4-pole

10mm

2

UPS 7500XHV

Output

1

220/230/240 V

38 amps

(as needed)

10 mm

2

Input

1

220/230/240 V

50 amps

63 amps / 2-pole

16 mm

2

Input

3

380/400/415 V

18 amps/ phase
when online, 50
amps on L1 in
bypass

63 amps/ 4-pole

16 mm

2

UPS 10000XHV

Output

1

220/230/240 V

50 amps

(as needed)

16 mm

2

Advertising