AIR CONNECTIONS

SUPPLY
Connect air supply to 1/4 NPT port marked "IN." If the above specifications are not met, possibility of internal clogging
exists. Also see MAINTENANCE section.

OUTPUT
Connect output to 1/4 NPT port marked "OUT."

GAUGE
The plugged 1/8 NPT port in the base of the transducer is internally connected with the "OUT" port. A pressure gauge can be
attached to this port to monitor output pressure.

CONTENTS
Air Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 1
Pressure Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 2
Mounting

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 2

Direct Mounting
Mounting Kits

Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 3

Precautions to be observed during installation

Calibration

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 4

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 5
Agency Approvals, Special Notes, and Cautions . . . . . . . . . . . . . . . . . .Page 5 & 6
Kits

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 7

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 8

WARNING

In order to get optimal service from this transducer and ensure warranty coverage the following MUST be followed:

The supply air quality to this instrument must be instrument quality air as defined by ISA Standard 57.0.01-1996.

1.

Dew point not higher than 35˚F.

2.

No particulates larger than 3 microns in size.

3.

Maximum oil content of 1 ppm.

No mechanical adjustments or calibrations are necessary or allowed. All calibration MUST be done with electrical poten-
tiometers on the enclosed circuit board only. See “CALIBRATION” section of instructions for more information.

M-4109/1104 IP510, EP510, IP511, EP511 SERIES

A

3

TABLE 1: SUPPLY PRESSURE REQUIREMENTS

Standard Output

Calibration

0-2

PSI

0-5

PSI

0-30

PSI

0-60

PSI

0-100

PSI

0-120

PSI

1-17

PSI

3-9

PSI

3-15

PSI

3-27

PSI

6-30

PSI

Transducer

Supply Pressure

20-45

PSI

20-45

PSI

50-90

PSI

80-120

PSI

110-130

PSI

130-140

PSI

30-70

PSI

20-100

PSI

20-100

PSI

35-100

PSI

35-100

PSI