47 icos, 72 l.......a........ (overheat error), 73 l ..... (fan error) – IDEAL INDUSTRIES ICOS HE18 User Manual

Page 47: 74 h ..... (flow thermistor error)

Advertising
background image

47

icos -

Installation & Servicing

FAULT FINDING

F

AUL

T FINDING F

AUL

T FINDING F

AUL

T FINDING F

AUL

T FINDING F

AUL

T FINDING

Does the pump setting give a differential

across the boiler in excess of 25

o

C ?

Can the overheat condition be reset by pressing

the boiler reset button when the system is cold ?

YES

YES

NO

72 L.......A........

(OVERHEAT ERROR)

Fill and vent the system and open all

isolation valves

Is the boiler and CH system filled with

water and all isolation valves open ?

NO

Replace overheat thermostat

73 L....8..... (FAN ERROR)

Is nominal 330 V DC present across
red and blue at the fan connector as

reset button is pressed?

Replace fan

YES

NO

Replace harness

74 H.....1.....

(FLOW THERMISTOR ERROR)

YES

Is there continuity between the

PCB and the thermistor ?

Check resistance, using a suitable multimeter

connected across the thermistors terminal pins

At 25

o

C

expect

9,700 - 10,300

Ohms

At 60

o

C

expect

2,400 - 2,600

Ohms

At 85

o

C

expect

1,000 - 1,100

Ohms

Remove the boiler flow thermistor from the CH flow

pipe and disconnect thermistor wires.

Are the thermistor values correct ?

Replace the thermistor

NO

NO

YES

Replace PCB

Check and replace wiring as necessary

Replace PCB

YES

Is 14V DC present

across yellow and pink

at the fan connector?

Check wiring harness for continuity. Is there continuity?

NO

YES

NO

Replace the system pump

Increase the pump setting.

Is differential now below 25

o

C ?

YES

OK

NO

YES

Set CH control knob to maximum.

If the overheat trips again measure the flow temp:

Over 90

o

C Check control thermistor

(Refer to Frame 71) .

Under 90

o

C Replace overheat 'stat

NO

Note.
With V9 Primary Control PCB, overheat LA/HA or H9/L9 when
reset will display 3 horizontal lines and will not attempt to refire
until the temperature in the heat exchanger drops below 50

o

C.