Horizontal left, Upflow downflow, Horizontal right – Johnson Controls TM9V120D20MP11 User Manual

Page 2

Advertising
background image

Furnace is multi-position and may be installed in any of the configurations shown.

Ensure that all PVC venting has at least 1/4” per foot slope towards the furnace.

The furnace condensate pan is self priming and contains an internal trap.

.

Do not install an external condensate trap

When drain hose routing changes are required (shown in red), be sure to cap
all unused openings.

If rerouting hoses - excess length should be cut off so that no sagging loops will
collect and hold condensate, which will cause the furnace to not operate.

Move rain gutter hose

to this position.

HORIZONTAL LEFT

Move pressure switch

hose to this position.

NOTE: May require the

longer hose that is

provided with wider

cabinets.

Change condensate drain

connection to the 90° fitting provided.

Move condensate drain hose to this position.

Move rain gutter hose to this position

NOTE: May require hose extension that

is provided with wider cabinets.

UPFLOW

DOWNFLOW

Move condensate drain

hose to this position.

For downflow applications, the gas

valve must be rotated upwards.

Inducer must be rotated 90° in

either direction for this installation.

HORIZONTAL RIGHT

Move pressure switch

hose to this position.

Change condensate drain

connection to the 90° fitting provided.

Move rain gutter hose

to this position.

Move condensate drain

hose to this position.

Move rain

gutter hose

to this position.

Move pressure switch

hose to this position.

NOTE: May require the

longer hose that is provided

with wider cabinets.

AIRFLOW

AIRFLOW

MOST COMMON INSTALLATION CONFIGURATIONS (MORE OPTIONS AVAILABLE

WHICH IS COVERED IN THE INSTALLATION MANUAL)

WITH INDUCER ROTATION,

Rain

Gutter

Hose

Pressure

Switch

Hose

Condensate
Drain Hose

For 100 & 120K input furnaces, the condensate

drain is factory set toward the left casing outlet.

For 060 & 080K input furnaces, the condensate

drain is factory set toward the right casing outlet.

MULTI-POSITION CONFIGURATION INFORMATION:

1

2

3

4

1

2

5

4

3

1

2

3

4

In upflow and downflow installation - Condensate drain hose may go out either side.

AIRFLOW

5

Move rain gutter hose