Johnson Controls TCGF24 User Manual

Tabular data sheet, Outdoor split system air conditioner 2 thru 5 tons

Advertising
background image

Johnson Controls Unitary Products

362564-UTD-B-0708

TABULAR DATA SHEET

Outdoor Split System Air Conditioner 2 Thru 5 Tons

MODELS: TCGF24* THRU 60

14.5 SEER – R-410A, 1 PHASE

All dimensions are in inches. They are subject to change
without notice. Certified dimensions will be provided upon
request.

Physical and Electrical Data

MODEL

TCGF24S41S1

TCGF30S41S1

TCGF36S41S1

TCGF42S41S1

TCGF48S41S1

TCGF60S41S1

Unit Supply Voltage

208-230V, 1

φ, 60Hz

Normal Voltage Range

1

1. Rated in accordance with ARI Standard 110, utilization range “A”.

187 to 252

Minimum

Circuit

Ampacity

16.8 18.4 19.1 23.9 27.9 35.9

Max. Overcurrent Device Amps

2

2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

25 30 30 40 45 60

Min. Overcurrent Device Amps

3

3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.

20 20 20 25 30 40

Compressor

Type

Scroll Scroll Scroll Scroll Scroll Scroll

Compressor
Amps

Rated

Load

12.8 14.1 14.1 17.9 21.1 27.5

Locked

Rotor

58 73 77 112

115

135

Crankcase

Heater

No No No No No No

Fan Motor Amps Rated Load

.8

.8

1.5

1.5

1.5

1.5

Fan

Diameter

Inches

22 22 22 24 24 24

Fan Motor

Rated

HP

1/8 1/8 1/4 1/4 1/4 1/4

Nominal

RPM

1075

1075 850 850 850 850

Nominal

CFM

2750 2800 3200 3600 3600 3700

Coil

Face

Area

Sq.

Ft.

13.1 17.4 17.4 20.0 21.4 24.0

Rows

Deep

1 1 1 1 1 1

Fin

/

Inches

23 23 23 23 23 23

Liquid Line Set OD (Field Installed)

3/8

3/8

3/8

3/8

3/8

3/8

Vapor Line Set OD (Field Installed)

3/4

3/4

3/4

7/8

7/8

1 1/8

Unit Charge (Lbs. - Oz.)

4

4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than

15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

3 - 2

3 - 7

3 - 10

4 - 4

4 - 9

5 - 9

Charge

Per

Foot,

Oz.

0.62 0.62 0.62 0.67 0.67 0.75

Operating

Weight

Lbs.

128 130 145 172 180 199

B

C

A

Unit

Model

Dimensions

(Inches)

Refrigerant Connection

Service Valve Size

A

1

1. Including Fan Guard.

B

C

Liquid

Vapor

24

28

29

29

3/8”

3/4”

30

36

29

29

36

36

29

29

42

34

33.6

33.6

7/8”

48

36

33.6

33.6

60

40

33.6

33.6

7/8”

2

2. Adapter fitting required for 1-1/8” line set.