PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting

line tubing.

2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.
4. For orifice or TXV matches requiring additional charge, the refrigerant needs to be weighed in for specific coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator +

adder for line set.

System Charge for Various Matched Systems

Outdoor Unit

TCGD18

S41S1(H)

TCGD24

S41S1

TCGD30

S41S1(H)

TCGD36

S41S1(H)

TCGD42

S41S1(H)

TCGD48

S41S1(H)

TCGD60

S41S1

Required Orifice or TXV

1,2

0.048/4F1

0.055/4F1

0.061/4F1

0.065/4G1

0.075/4G1

0.073/4H1

0.087/4J1

Factory Charge, lbs-oz

3 - 3

3 - 13

3 - 14

4 - 9

4 - 5

4 - 9

5 - 6

Indoor Coil

3,4

Additional Charge, oz

AHP18

0

AHP30

4

0

AHP36

2

0

AHP42

0

0

AHP/SHP60

0

0

AHX18

0

AHX30

4

0

AHX36

4

2

0

AHX42

8

2

AHX48

0

AHX60

4

AV*24

TXV + 0

AV*36

4

2

0

AV/SV*48

TXV + 2

0

AV/SV*60

TXV + 2

0

F4FP024

0

F4FP036

0

F4FP040

0

F4FV060

0

0

F5FP048

8

2

4

F5FP060

0

0

F6FP018

0

F6FP030

4

0

F6FP036

4

0

F6FP042

8

2

F6FP048

TXV + 2

0

F6FP060

4

FC/MC/PC/18

0

FC/MC/PC32

4

0

FC/MC/PC35

4

0

FC/MC/PC/36

0

FC/MC/PC37

4

2

0

FC/MC/PC43

4

2

0

0

FC/MC/PC48

8

2

4

FC/MC/PC60

0

0

FC/MC62

4

HC18

0

HC30

0

HC36

4

0

HC42

4

2

0

0

HC60

0

UC18

0

UC36

0

UC48

8

2

4

UC60

0

0

FOOTNOTES:

1. For applications requiring a TXV use 1TVM series kit.
2. Approved orifice shipped with outdoor unit.
3. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.

Models 12-48 require start kits for TXV matches.