SECTION III: FILTERS

FILTER INSTALLATION

All applications require the use of a field installed filter. All filters and
mounting provision must be field supplied.

Filters must be installed external to the furnace cabinet. DO NOT
attempt to install filters inside the furnace.

NOTE: Single side return above 1800 CFM is approved as long as the
filter velocity does not exceed filter manufacturer’s recommendation
and a transition is used to allow use on a 20x25 filter.

NOTES:

1. Air velocity through throwaway type filters may not exceed 300 feet per

minute (91.4 m/min). All velocities over this require the use of high velocity
filters.

2. Do not exceed 1800 CFM using a single side return and a 16x25 filter. For

CFM greater than 1800, you may use two side returns or one side and the
bottom or one side return with a transition to allow use of a 20x25 filter.

SIDE RETURN

Locate the “L” shaped corner locators. These indicate the size of the cut-
out to be made in the furnace side panel. Refer to Figures 13.

Install the side filter rack following the instructions provided with that
accessory. If a filter(s) is provided at another location in the return air
system, the ductwork may be directly attached to the furnace side
panel.

FIGURE 12: Dimensions

FRONT

33

A

LEFT SIDE

Combustion Air Inlet

Condensate Drain
(Downflow)

Vent Outlet

Thermostat
Wiring

28.5”

Gas Pipe
Entry

Electrical
Entry

Condensate
Drain

Thermostat
Wiring

RIGHT SIDE

Vent Outlet

Condensate Drain
(Downflow)

14”

1”

1.5”

23”

Combustion Air Inlet

Gas Pipe
Entry

Electrical
Entry

Condensate
Drain

Optional Return Air
Cutout (Either side)

29.5”

(For Cladded door add appoximately an additional .75”)

C

SUPPLY END

.56”

.56”

20”

B

3”

23.8”

.56”

Combustion
Air Inlet

Vent
Outlet

RETURN END

B

24.25”

Table 3: Cabinet and Duct Dimensions

BTUH (kW)

Input

Nominal

CFM (m

3

/min)

Cabinet

Size

Cabinet Dimensions (Inches)

Approximate

Operating Weights

A (in)

A (cm)

B (in)

B (cm)

C (in)

C (cm)

Lbs (kg)

60 (17.6)

1200 (34.0)

B

17 1/2

44.4

16 3/8

41.6

13 1/4

33.7

122 (55.3)

80 (23.4)

1200 (34.0)

B

17 1/2

44.4

16 3/8

41.6

14 3/4

37.5

126 (57.1)

80 (23.4)

1600 (45.3)

C

21

53.3

19 7/8

50.5

16 1/2

41.9

136 (61.7)

100 (29.3)

1600 (45.3)

C

21

53.3

19 7/8

50.5

18 1/4

46.4

142 (64.4)

100 (29.3)

2000 (56.6)

C

21

53.3

19 7/8

50.5

18 1/4

46.4

145 (65.8)

120 (35.1)

2000 (56.6)

D

24 1/2

62.2

23 3/8

59.4

21 3/4

55.2

156 (70.7)

Table 4: Recommended Filter Sizes (High Velocity 600 FPM)

CFM

(m³/min)

Cabinet

Size

Side

(in)

Bottom

(in)

1200 (34.0)

B

16 x 25

16 x 25

1600 (45.3)

C

16 x 25

20 x 25

2000 (56.6)

C

(2) 16 x 25

20 x 25

2000 (56.6)

D

(2) 16 x 25

22 x 25

FIGURE 13: Side Return Cutout Markings

Some accessories such as electronic air cleaners and pleated
media may require a larger side opening. Follow the instructions