Caution

Motor Load

1. The corrected horsepower should be close to but not exceed the contract

horsepower specified (see page 2). Determine corrected horsepower

with this equation:

Actual volts and amperage must be obtained with the fan running and the

specified rate of water flowing over the tower after the motor and Geareducer

have reached operating temperature (approximately 30 minutes of opera-

tion).

2. The blade pitch can be changed to obtain contract horsepower. A one

degree pitch change will change the power about eight horsepower. If

blades are repitched, follow pitching and fastener tightening instructions

detailed in the Fan Assembly section of this manual.

Measurements taken on motors operating with Variable Frequency

Drive controls may read up to 15% high from errors in measuring the

approximated sine wave. Instruments capable of measuring a squared

off wave form accurately should be used for measuring power in this

situation.

When checking and/or changing blade pitch or cycling fan in normal

operation, do not exceed 30 sec/hour total motor starting time as mo-

tor may be overheated.

Service

When contacting your Marley sales representative for repair or replacement

parts, please refer to the tower serial number.

Replacement blades can be installed without rebalancing. The fan series—

HP7i—and diameter are required when ordering replacement parts.

If rebalancing is required, return the fan hub to Marley for factory rebal-

ance. Obtain a Customer Return Material tag from your Marley sales

representative.

VOLTS

N

= Nameplate Volts

AMPS

N

= Nameplate Amperage

HP

N

= Nameplate Horsepower

DENSITY

D

= Design Air Density

HP

C

= Corrected Horsepower

VOLTS

A

= Actual Volts

AMPS

A

= Actual Amperage

DENSITY

A

= Actual Air Density

VOLTS

A

× AMPS

A

× DENSITY

D

VOLTS

N

× AMPS

N

× DENSITY

A

HP

C

=

×

HP

N

Manual 92-1471E