Printer accessories, Sentry printer, Key event report – Sierra Monitor Corporation Sentry SPL69207 User Manual

Page 2: Calibration report, History report, Warm start report, Voltage) and with span gas (2, Voltage) is sufficient to get adequate resolution

Advertising
background image

PRINTER

ACCESSORIES

KEY EVENT REPORT

When any module reading exceeds a preset minimum
level an Event Report is generated. After the sensor is
above the minimum level, any change greater than a pre-
set change concentration will cause another Event Re-
port to print. The Event Report prints all module num-
bers and their present reading. This concise record pro-
vides information for better decision-making before an
alarm level is reached.

CALIBRATION REPORT

The Calibration Report prints automatically upon comple-
tion of calibration. The report indicates which gas type
was calibrated, the gas concentration and the planned
frequency of calibration. For each module the report lists
the percent change during calibration, the peak concen-
tration and the zero and span sensor voltages. Module
sensitivity is also checked. Proper sensitivity requires
that the voltage difference obtained in air (1

st

voltage) and

with span gas (2

nd

voltage) is sufficient to get adequate

resolution.

HISTORY REPORT

The History Report lists the last time each significant
event has occurred. This includes system power inter-
ruption, history reset, alarm and concentration informa-
tion for each sensor, calibration time for each sensor and
an error log. A History Report can be printed each time a
programmed Status Report is printed. These records are
useful in establishing the presence of gas during the pe-
riod and documenting the company’s due diligence in its
gas monitoring efforts.

WARM START REPORT

At any time the system is warm started due to a power
failure, a report is generated to show the system soft-
ware configuration, the result of an internal diagnostic
sequence and the power down and power up date and
times.

----------------------------------------

ID:A <KEY EVENT REPORT> 12/17 14:27

1 2 3 4 5 6 7 8

05 03 23 29 07 02 01 02

----------------------------------------

ID:A <KEY EVENT REPORT> 12/17 14:35

1 2 3 4 5 6 7 8

07 03 23 25 08 02 01 02

----------------------------------------

ID:A <KEY EVENT REPORT> 12/17 14:37

1L 2 3 4 5L 6 7 8

11 03 23 25 12 02 02 03

----------------------------------------

ID:A <KEY EVENT REPORT> 12/17 14:40

1H 2 3 4 5L 6 7 8

21 04 23 24 12 03 09 02

----------------------------------------

ID:A <KEY EVENT REPORT> 12/17 14:45

1H 2 3 4 5L 6 7L 8

35 04 22 24 13 03 20 02

----------------------------------------

ID:A <KEY EVENT REPORT> 12/17 14:56

1H 2 3 4 5 6 7L 8

- - - - - - - - - - - - - - - - - - - - - - - - - - - -

< C A L I B R A T I O N R E P O R T >

I D : A U S E R # = 0 1 2 / 1 8 1 0 : 0 3

G A S T Y P E : C O M B

C A L I B C O N C = 6 0

C A L F R E Q = 9 0 D A Y S

G L O B A L C A L I B : O F F

> M O D U L E # = 2

% C H A N G E = + 0 1 % F S

P E A K C O N C . = 6 1

1 S T V O L T A G E = + 0 . 0 7 3

2 N D V O L T A G E = + 0 . 8 1 0

> M O D U L E # = 3

% C H A N G E = - 1 5 % F S

P E A K C O N C . = 4 5

1 S T V O L T A G E = + 1 . 6 4 9

2 N D V O L T A G E = + 1 . 3 9 5

> M O D U L E # = 4

L O W S E N S I V I T Y

% C H A N G E = + 0 1 % F S

P E A K C O N C . = 6 1

1 S T V O L T A G E = + 0 . 0 7 3

2 N D V O L T A G E = + 0 . 8 1 6

----------------------------------------

<HISTORY REPORT>

ID:A USER # =1 12/17 15:08

HISTORY RESET AT: 02/01 10:59

POWER DOWN AT:12/17 13:34

POWER UP AT:12/17 13:44

MODULE 1 PPM H2S

LOW ALARM 12/13 05:07

HIGH ALARM 12/17 15:07

LOWEST CONC = 00 12/16 10:59

HIGHEST CONC = 23 12/17 15:07

LAST CALIBRATED :02/15 14:33

MODULE 2 %LEL COMB

LOW ALARM 12/10 12:08

HIGH ALARM 00/00 00:00

LOWEST CONC = 00 12/16 11:36

HIGHEST CONC = 45 12/10 12:35

LAST CALIBRATED :02/16 11:35

MODULE 3 %LEL COMB

LOW ALARM 12/10 11:57

HIGH ALARM 12/10 12:20

LOWEST CONC = 00 03/16 10:59

Sierra Monitor Corp. 1991 Tarob Ct., Milpitas, CA 95035, USA, 408-262-6611, 800-727-4377, FAX: 408-262-9042

Web Site: http://www.sierramonitor.com E-Mail: [email protected]

© 2009 by Sierra Monitor Corporation

Sentry Printer

SPECIFICATIONS for Printer 5301-10

PRINTING:

Direct Thermal

CHARACTERS per LINE: 16 cpi, 24 cpi, 32 cpi, 42 cpi
CHARACTER SIZE

9x24 dots, 12x24 dots, 16x24 dots,
24x24 dots

RESOLUTION

203 dpi, 8 dots/mm

PRINT WIDTH

2-inch (48 mm)

PRINTING SPEED

50 mm/sec

INTERFACES

Sentry Controller

Serial RS232

Sentry Commander Parallel
FieldServer

Serial RS232

DIMENSIONS

3.2 x 3.95 x 2.2 inches (80 x 75 x 55
mm)

PAPER

Thermal Roll 57 mm wide; 40 mm
diameter, spproximately 20m long

POWER

12V-24V DC

OPERATIING TEMP.

32 - 113

o

F (0-45

o

C)