Chapter 2 Installation

Series 780S Instruction Manual

2-8

IM-78S-B

4-20 mA Output Wiring
The 4-20 mA current loop output can be self-powered (non-isolated)
or externally powered (isolated). To use the 4-20 mA isolated output,
an external 12 to 36 VDC power supply is required. The maximum
loop resistance (load) for both types of current loop outputs are de-
pendent upon the supply voltage and are given in Figure 2-10.

R

load

is the total resistance in the loop, including the wiring resis-

tance. To calculate R

max

, the maximum R

load

for the loop, use the

maximum loop current, 20 mA. The voltage drop in the loop due to
resistance is 20 mA times R

load

and this drop is subtracted from the

input voltage. Thus:

R

max

the maximum load resistance = 50 * (V

supply

– 7.5V)

To use an external power supply for an isolated 4-20 mA output, con-
nect as shown in Figure 2-11 or Figure 2-13. For an internally pow-
ered, non-isolated 4-20 mA output, connect as shown in Figure 2-12
or Figure 2-14.

Figure 2-10. Load Resistance Versus Input Voltage

V

suppl

y

R

max

(Volts)

(Ohms)

11 (min)

175

12

225

15

375

18

525

24

825

30

1,125

36 (max)

1,425