10

Method B

1. Disconnect power to the heater control panel using standard lockout
procedures for safety.

2. Drain basin until the water level is below the probe allowing removal of
the probe. Make sure water still covers the heater elements.

3. Place the probe in a container of ice water making sure both metal parts
of the probe are submerged but not the cord.

4. Energize the heater control panel. Allow 5 min. for the probe tempera-
ture to stabilize.

5. An audible CLICK should be heard as the heater contactor engages. If
this does not happen, refer to the

Troubleshooting section.

/ Operation /