Safety

The inverter is electronically protected. But protection against polarity inversions of the
battery occurs with an internal fuse, except for AJ 2100-12 inverter, which has no
fuse

. The following table will show you the different failures and their consequences.

FAILURE CONSEQUENCE

SOLUTION

Low battery voltage
Voltage < 1.8V/cell

Inverter momentarily
stopped, the green
indicator blinks.

Automatic restart when the
battery voltage rises

Deep discharged battery
(voltage <1,5V/cell)

Inverter stopped

Inverter should be manually
restarted when the battery
as reach 2V/cell

Overheating Inverter

momentarily

stopped, the green
indicator blinks.

Automatic restart when the
temperature reaches the
normal range.

Battery over voltage

Inverter stopped.

Wait until the battery voltage
reaches the correct level.
Push the ON/OFF switch to
reactivate the inverter

Short circuit in the outlet Inverter stopped.

Eliminate the short circuit.
Push the ON/OFF switch to
reactivate the inverter.

Overload Inverter

stopped.

Use

the inverter only in the

range of its nominal power.
Regular use in overload
power diminished the
lifetime of the inverter.
Push the ON/OFF switch to
reactivate the inverter.

Inversion of the battery
polarity

Internal fuse broken down Back to manufacturer for

testing