State Industries GP6 50 User Manual

Page 20

Advertising
background image

20

plannInG the vent sYsteM

Plan the route of the vent system from the discharge of the blower

to the planned location of the vent terminal. Refer to VAA instruction

on page 24 while planning the vent system.
1. Layout total vent system to use a minimum of vent pipe and elbows.
2. This water heater is capable of venting flue gases equivalent to

25’ (7.6 m) of 2” pipe, 65’ (19.8 m) of 3” pipe, or 128’ (39.0 m) of

4” pipe as listed in Table 2.

taBle 2.

Number of

2” Maximum

3” Maximum

4” Maximum

90° Elbows Pipe - ft. (m)

Pipe - ft. (m)

Pipe - ft. (m)

1

20 (6.1)

60 (18.3)

120 (36.6)

2

15 (4.6)

55 (16.8)

112 (34.1)

3

10 (3.0)

50 (15.2)

104 (31.7)

4

--

45 (13.7)

96 (29.3)

5

--

40 (12.2)

88 (26.8)

6

--

35 (10.7)

80 (24.3)

The minimum vent lengths for each of the pipe sizes is one 90° on top of

the unit plus 2’ (61cm) of straight pipe and the appropriate termination.
note: The equivalent feet (m) of pipe listed above are exclusive

of the termination. That is, the termination, with an installed

screen, is assumed to be in the system and the remainder of the

system must not exceed the lengths discussed above.

3. The blower discharge adapter is made to accept only straight

sections of 2” pipe. To start, a minimum of 2 inches (5.1 cm) of 2”

pipe must be attached to the blower discharge, see Figure 17.

If using 2” inch vent pipe:

A minimum of 2 inches (5.1 cm) must be attached to the blower

before the first elbow. After the first elbow add the additional

venting required for the installation. The total system cannot

exceed the lengths discussed above, where each elbow is equal

to 5 feet (1.5 m) of straight pipe.

If using 3” or 4” inch vent pipe:

Two inches (5.1 cm) of pipe must be attached to blower discharge before

adding a reducer to acquire desired pipe diameter. An appropriately

sized 45 degree schedule 40 DWV elbow (field supplied) vent terminal

must be obtained with an equivalent screen (supplied in vent kit).

The total system cannot exceed equivalent pipe lengths discussed

above where each elbow is equal to 5 feet (1.5 m) of straight pipe

(3” vent pipe) or 8 feet (2.4 m) of straight pipe (4” vent pipe).

note: This unit can be vented with PVC pipe materials (DWV

ASTM-D2665 or CSA B181.2; Schedule 40, 80, 120 ASTM-D1785 or

CSA B137.3; or SDR Series ASTM-D2241 or CSA B137.3), CPVC pipe

materials (CPVC41 ASTM-D2846 or CSA B137.6; Schedule 40, 80

ASTM-F441 or CSA B137.6; or SDR Series ASTM-F442), ABS pipe

materials (Schedule 40 DWV ASTM-D2661 or CSA B181.1). Fittings,

other than TERMINATION should be equivalent to PVC-DWV fittings

meeting ASTM D-2665 (Use CPVC fittings, ASTM F-438 for CPVC

pipe and ABS fittings, ASTM D-2661/3311 for ABS pipe). If CPVC or

ABS pipe and fittings are used, then proper cement must be used for

all joints, including joining pipe to Termination (PVC Material). If local

codes do not allow use of PVC termination when a material other than

PVC is used for venting, then an equivalent fitting of that material may

be substituted if screen in PVC terminal is removed and inserted

into new fitting.
PVC Materials should use ASTM D-2564 Grade Cement; CPVC

Materials should use ASTM F-493 Grade Cement and ABS Materials

should use ASTM D-2235 Grade Cement.
If water heater is being installed as a replacement for an existing power

vented heater in pre-existing venting, a thorough inspection of existing

venting system must be performed prior to any installation work. Verify

that correct material as detailed above has been used, and that minimum

or maximum vent lengths and terminal location as detailed in this manual

have been met. Carefully inspect entire venting system for any signs

of cracks or fractures, particularly at joints between elbows and other

fittings and straight runs of vent pipe. Check system for signs of sagging

or other stresses in joints as a result of misalignment of any components

in system. If any of these conditions are found, they must be corrected in

accordance with venting instructions in this manual before completing

installation and putting water heater into service.
note: a. For water heaters in locations with high ambient

temperatures (above 100°F) it is recommended that CPVC or ABS

pipe and fittings be used.

B. A 22.5 degree elbow (2” vent pipe) or a

45 degree elbow (3” and 4” vent pipe) with an installed screen VENT

TERMINAL must be used in all cases.
4. There will be some installations where condensate will be formed

in the horizontal runs of the vent system. This condensate will

run into the condensate boot attached to the blower and out the

fitting. The water heater is shipped with condensate hose that

attaches to the fitting on the condensate boot. No other Tee or

fitting is required. See Figures 17, 20 and 21.

condensate

This water heater is a condensing unit and requires a drain to be

located in close proximity to allow condensate to drain safely. One hose

from blower housing, two flexible hoses from blower outlet adaptor,

along with another flexible hose from VAA if installed, run to barb fittings

on vent pipe assembly #2. Hose is clamped by rubber clips and flexible

hoses by a clamp on jacket top cover. See Figure 17. Condensate

drains from the unit at the exhaust tee located at the bottom of the unit

(see figure 16). Condensate from this water heater is mildly acidic.

Please note that some local codes require that condensate is treated

by using a pH neutralizing filter prior to disposal.
NOTE: It is important that the field supplied drain lines beyond the 1/2”

adaptor of vent pipe assembly #1 should be installed continuously

tilted downward toward an appropriate drain. See Figure 16. If these

instructions are not followed or if condensate drain line is blocked, water

will spill from condensate trap. Do not block the holes in the hex plug on

top of a small tee in vent pipe assembly #1. As with every water heater

installation, a drain pan should be used to prevent water damage to

surrounding area. If necessary, a condensate pump with an incorporated

reservoir may be used to pump water to an appropriate drain. To avoid

condensate spillage, select a pump with an overflow switch.
Caution must be used to ensure that drain is free and clear of debris

and will not allow backflow through the condensate drain line.

Consideration must be given to avoid freezing of the condensate lines

which could result in excessive build up of condensate inside the water

heater. Waterproof heat tape may be required to prevent freezing of

condensate lines. Please ensure that the outlet of condensate drain

does not create a slippery condition which could lead to personal

injury. Care should be taken to ensure there is no kink or twist in any

condensate hose. If a VAA is not installed, the unused barb fitting in

vent pipe assembly #2 should be plugged using one of the break-

away plugs.

Breathing Hazard - Carbon Monoxide Gas

Do NOT block the holes in the hex plug of vent pipe

assembly #1.

Do NOT elevate any portion of the field supplied drain

line beyond the 1/2" adaptor above the adaptor. This

must be true for entire length of the drain line including

the exit into an appropriate drain.

Condensate lines must be free and clear of debris and

must not allow back flow through drain line. Condensate

lines must be able to flow freely to an appropriate drain.

Do not allow condensate lines to become crimped closed.

Analyze entire vent system to make sure that condensate

will not become trapped in a section of vent pipe and

therefore reduce open cross sectional area of vent.

Breathing carbon monoxide can cause brain damage or death.

Always read and understand instruction manual.

Advertising