SECO-LARM USA EAP-5D1 User Manual

Eap-5d1, Features, Power

Advertising
background image

AC power failure supervision relay.
Battery failure supervision relay.
Selectable 2.2K-Ohm End-of-Line (EOL) resistor for AC failure
and battery failure supervision relays.
Selectable delay timer (5 sec., 5 min., 5 hours) for AC failure
supervision relay.
LED overload indicator and automatic shutdown for short-
circuit protection.
Over-current fuse-protected AC input.
Built-in back-up battery charger
Automatically switch to back-up battery if AC fails.
Individual AC input and DC output LED status indicators.

1.949.261.2999 (CA & Int’l) 1.800.662.0800 Fax: 1.949.261.7326
Email: [email protected] Website: www.seco-larm.com

16842 Millikan Avenue, Irvine, CA 92606

AccessControlPowerSupply.cdr

Features:

Field selectable for 12VDC or 24VDC output.
Operating voltage input 110~240 VAC.
Adjustable voltage range (11~15 VDC, 23~26 VDC) to
compensate for voltage drop.
Supply current: 5 Amps @ 12VDC, 4.5 Amps @ 24VDC.
AC input fuse rating 3.15 Amps (glass fuse).
DC output overload sensing with red LED indicator and
automatic shutdown during short circuit.

Power

Heavy-duty steel case to protect the power connections.
Removable steel cover for easy access.
Ventilation holes to prevent heat build-up.
Enclosure has enough room for two 7AH batteries.
6-foot power cord and battery leads included.
Dimensions: 12-3/16” x 12-7/16” x 3-9/16”.
Knock-out on the cover for optional cam lock.

Enclosure

Dimensions: 12-3/16" x 12-7/16" x 3-9/16"

®

EAP-5D1

1 Output, 5A@12VDC, 4.5A@24VDC

The SECO-LARM policy is one of continual development. For that reason, SECO-LARM reserves the right to change prices and specifications without notice. SECO-LARM is not responsible for misprints.

Copyright 2007 SECO-LARM U.S.A., Inc. All rights reserved.

Connections:

DIP switch

for 12 or 24 VDC

output selection

VR1 rotary knob

for DC output

voltage range

adjustment

AC failure
delay timer
DIP switch

End-of Line
(EOL) 2.2K Ohm
resistor DIP switch

AC input fuse

AC input LED

status indicator

SL-126A

Power Supply

DC output LED
status indicator*

Back-up

battery terminal

AC failure Supervision

Relay Output to

Audio/Visual

warning device

Battery failure & low battery

Supervision Relay Output to

Audio/Visual warning device

DC output

terminal block

12 VDC Battery

(Optional)

+

-

Power Supply

Battery presence

and low battery

monitor DIP switch

110~240 VAC

INPUT