Adjusting Fan Blade Pitch

The trial pitch is the calculated setting for design conditions
(water rate , heat load, air density, and brake horsepower)

. The trial

pitch is provided by SPX (see page 2).

1–Select a position on the fan circumference and rotate each blade
to this common location when setting or checking blade pitch. Sup-
port the blade tip to maintain a common rotation plane while setting
the fan pitch. The pitch is set

3

16

" (5 mm) inboard of the blade tip

by placing a protractor on top of a parallel sided straight edge that
extends across blade width as shown in

Figure 4.

2–Be sure all blades are positioned correctly on hub, then set the
pitch. Blades should be within ±

1

4

° of the desired pitch angle. After

the desired setting is obtained, progressively tighten the hardware
according to

Table 5. Recheck the pitch angle. If required, loosen

the hex nuts and reset the pitch as necessary until the proper pitch
angle is obtained.

Note

Figure 4

Table 5

Bolt

Diameter

3

8

"

5

8

"

ft·lb

ƒ

40

100

N·m

55

136

Torque Wrench Setting