Appendix – Siemens vacuum circuit breaker 38-3AH3 38 kV User Manual

Page 63

Advertising
background image

Appendix

Continuous current

Circuit breaker type

A

38-3AH3-31

38-3AH3-40

38-3AH3-1500

1,200

800 (364)

850 (387)

800 (364)

2,000

900 (409)

950 (432)

900 (409)

3,000

1,000 (455)

1,050 (478)

1,000 (455)

Table 10: Type 38-3AH3 vacuum circuit breaker weight in lbs (kg)

1, 2, 3

Footnotes:

1.

Weight estimates are for circuit breaker only.
Add 125 lbs (57 kg) for packaging.

2.

Weight and dimensions are approximate..

3.

Approximate circuit breaker dimensions in
inches (mm) (W x D x H):

Net 44" (1,117 mm) x 46" (1,168 mm) x 51"
(1,294 mm)
Packed for shipment separate from switchgear:
48" (1,218 mm) x 48" (1,218 mm) x 60"
(1,522 mm).

Spring charging time

≤ 10 s

Close time from energizing close coil at rated
control voltage to contact touch (last pole)

38 kV

≤ 70 ms

Opening time from energization trip coil
at rated control voltage to contact part
(last pole), not including arcing time

5-cycle interrupting time (83 ms)

38 kV

≤ 56 ms

3.5-cycle interrupting time (58 ms)

38 kV

≤ 43 ms

3-cycle interrupting time (50 ms)

38 kV

≤ 38 ms

Table 11: Circuit breaker operating times (type 3AH3 operator)