SPX Cooling Technologies MARLEY HP700 User Manual

Page 9

Advertising
background image

9

141

102

143

142

300

145

142

146

144

142

Hub Cover Installation

Install the hub cover as shown in

Figure 1 and Figure 7. Tighten all

hex nuts to 15 ft·lb

ƒ

(20 N·m) torque.

Figure 7

Fan Maintenance

Preventative maintenance will prolong useful life and assure contin-
ued trouble-free operation. After the first week and subsequently
at six month intervals:
• Torque all hardware to specifications referenced in this manual.
• Visually inspect the fan for airborne debris damage, contact with
fan cylinder segments, and corrosive attack. Correct any situations
determined detrimental to fan operation.
• Remove any accumulated scale or dirt.
• Clear blade drain holes.

Advertising