Mounting
The 2112/24TSRB detector is supplied with a mounting
bracket that permits the detector to be mounted:
1. To a single gang box, or
2. Directly to a 3

1

/

2

-inch or 4 inch octagonal box, or

3. To a 4 inch square electrical box by using a plaster ring.

Tamper-resistant Feature
This detector includes a tamper-resistant feature that pre-
vents its removal from the bracket without the use of a
tool. To make the detector tamper-resistant, remove the
smaller tab by breaking it at the scribed line on the tamper
resistant tab on the detector mounting bracket (see Figure
2), then install the detector. To remove the detector from
the bracket once it has been made tamper resistant, use
a small screwdriver to depress the tamper-resistant tab,
located in the slot on the mounting bracket, and turn the
detector counterclockwise.

Wiring Installation Guidelines
All wiring must be installed in compliance with the Na-
tional Electrical Code, applicable local codes, and any spe-
cial requirements of the local authority having jurisdiction.
Proper wire gauges should be used. The conductors used
to connect smoke detectors to control panels and accessory
devices should be color-coded to reduce the likelihood of
wiring errors. Improper connections can prevent a system
from responding properly in the event of a fire.

TAMPER SLOT

(DEPRESS TAB TO

REMOVE DETECTOR)

TAMPER RESISTANT TAB

(CUT OFF SMALL TAB TO

ACTIVATE TAMPER-RESIST

FEATURE)

ALIGNMENT

ARROWS

Figure 1. Surface mounting of 2112/24TSRB smoke
detector on 3

1

/

2

-inch and 4-inch octagonal box:

A78-2563-00

Figure 2. Smoke detector mounting bracket:

A78-2333-01

The screw terminal block accepts 14 – 22 gauge wire. For
best system performance, all wiring should be installed in
separate grounded conduit. Do not mix fire system wiring
in the same conduit as any other electrical wiring. Twisted
pair may be used to provide additional protection against
electrical interference.

Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel specifications for the total loop resistance
allowed for the control panel being used before wiring the
detector loops.

Wire connections are made by stripping about 1/4 inch of
insulation from the end of the feed wire, inserting the wire
into the appropriate terminal, and tightening the screw to
secure the wire in place.

NOTE: Trouble relay must be wired last in the circuit.

Installation

WARNING

Remove power from the control unit or initiating device
circuits before installing detectors.

1. Wire the plug-in screw terminal block per Figure 3 and

plug the terminal block into the detector.

2. Align the arrows on the detector with the arrows on the

mounting bracket.

3. Turn the detector clockwise in the mounting bracket un-

til it clicks into place.

4. After all detectors have been installed, apply power to

the control unit or initiating device circuits.

5. Test the detector as described in TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.