Ratings and specifications typical piping diagram, Electrical – Slant/Fin Monitron EH Boilers User Manual

Page 4

Advertising
background image

Boiler

Model No.

SINGLE

PHASE
* KW at

240 VAC

SINGLE

PHASE

D.O.E

Capacity

*(Btu/hr) at

240 VAC

Neutral Lug
Size (AWG)

Solid

Cu ¶ AL

Stranded

Cu ¶ AL

SINGLE PHASE –– THREE WIRE

Main Lug

Size (AWG)

CU ¶ AL

Grounding

Lug Size

(AWG)

Cu

¶ AL

† ** Heater

Amps at

240 VAC

THREE PHASE –– FOUR WIRE 208 VAC WYE §

KW at

208 VAC

D.O.E

Capacity
(Btuh) at
208 VAC

Main Lug

Size (AWG)

CU ¶ AL

Grounding

Lug Size

(AWG)

Cu

¶ AL

† Heater

Amps at

208 VAC

EH8S

8

27000

14-12

12

6-2/0

14-4

6-4

33

–––

–––

–––

–––

–––

–––

EH10S

10

34000

14-12

12

6-2/0

14-4

6-4

42

–––

–––

–––

–––

–––

–––

EH12S

12

41000

14-12

12

6-2/0

14-4

6-4

50

9.012

31000

6-2/0

14-4

6-4

25.1

EH16S

16

55000

14-12

12

6-2/0

14-4

6-4

67

12.016

41000

6-2/0

14-4

6-4

‡38.1

EH20S

20

68000

14-12

12

6-2/0

14-4

6-4

83

15.020

51000

6-2/0

14-4

6-4

‡48

EH24S

24

82000

14-12

12

6/2/0

14-4

6-4

100

18.024

62000

6-2/0

14-4

6-4

‡60

EH28S

28

96000

14-12

12

2-250 MCM

14-4

6-4

117

21.028

72000

6-2/0

14-4

6-4

‡60

EH32S

32

109000

14-12

12

2-250 MCM

14-4

6-4

133

24.032

82000

6-2/0

14-4

6-4

‡73

EH40S

40

137000

14-12

12

2-250 MCM

6-2/0

–––

167

30.040

103000

6-2/0

14-4

6-4

‡95.4

* Multiply by 0.751 for values at 208 volts AC.
** Multiply by 0.867 for values at 208 volts AC.
† For total current add, to the value shown in the table, the current draw for

circulator and/or zone valve transformer (12 Amp. max.),

‡ Leg with the highest value of line current of an unbalanced 3 phase load.

¶ Aluminum conductors may be used, lug size, conduit size, ampacity and all

applicable codes permitting. However, aluminum conductors may not be
used for model EH-40 single phase.

§ 3 phase 240V special model also available.

Consult factory for information.

“135S” for single phase, 120V/240V, 120V/208V WYE. 3 wire (see
note (1) below) with control circuit breaker.
“345S” for three phase, 120V/208V WYE. 4 wire (see note (1)
below) with control circuit breaker.
Note No. 1: Voltage of any line to ground cannot exceed
125 VAC.

Example: EH-20-135S=20KW boiler for 120V/240V.
120V/208V Single Phase 3 wire.

Specify Model as follows: Model Number. Single or three Phase.

ELECTRICAL

FOR USE WITH TWO-WAY ZONE VALVES

NOTES:

1. Optional blocking gate valve and hose end valve

used (with drain valve) for fast fill and purge of
system.
IMPORTANT Close bypass line valve
(if used) during purging.

2. Circulator should not be installed at lowest point

of piping.

3. There should be no elbows, tees, or change of

pipe size for at least 5 diameters of pipe size
(see table below) upstream and downstream of
flow switch.

Boiler Model

Flow Switch

McDonnell

& Miller No.

Pipe
Size

Minimum Length of

Straight Pipe Upstream

and Down-Stream

of Flow Switch

EH-40

FS8W

1

1

4

IN.

8

1

2

IN.

EH-8 Thru EH-32 FS4-3T3-1

1 IN.

6

1

2

IN.

© Slant/Fin Corp. 2003. Printed in U.S.A. 1203. Publication EH-10

RATINGS AND SPECIFICATIONS

TYPICAL PIPING DIAGRAM

Single branch circuit for 3 wire 120/208 V WYE, 120/240 Volt a.c.
single phase, 60 Hz or for 4 wire 120/208V WYE three
phase, 60Hz a.c. See note (1) above.

Circulator relay 12 AMP Max, 120V a.c.

Heating elements: Low-density replaceable. Copper sheathed
and silver brazed base.

Relays: Heavy-duty contactors, 48 AMP U.L. rating