Sierra Monitor Corporation 3140-01 User Manual

Sierra Monitor Corporation Safety

Advertising
background image

Model 3140-01

Flame Detector Tester

Sierra Monitor Corporation - 1991 Tarob Court, Milpitas, CA 95035 USA (408) 262-6611 (800) 727-4377 Fax: (408) 262-9042

www.sierramonitor.com

Email: [email protected]








Description

The Model 3140 simulates a UV/IR flame
signature by emitting a steady state UV signal
and a modulated IR signal at a flicker frequency
of 5 to 10 Hz. This simulation will cause the
Model 3100 flame detector to report an alarm.
Like the Model 3100 detector the 3140 is
designed for use in Hazardous environments.

The Model 3140 is intended for use in those
applications where regular testing, as required
by NFPA 72, is performed or where the use of
a real fire is impractical. The 3140 is rated over
a wide operating temperature range for those
applications where Flammable materials may
be present.

Features

Wide operating temperature range.

Surfaces are smooth, non-shedding, and
scuff resistant.

Conforms to the operational specification
for the Model 3100 Flame Detector.

Generates an Industry Standard UV/IR
Signature for use with a variety of devices.

Uses commercially available 9-volt batteries
(not a proprietary power module).

Specifications

Sensitivity

Typically alarms a 3100 in 3
seconds when viewed on-axis @
2-15 feet

Housing

Aluminum with Red Epoxy Paint

Power

Standard 9-Volt Battery

Operating
Temperature

-40° to 85° C.

Operating
Humidity

10% to 90%.

Red LED

A flashing LED indicates Operation

Spectral
Emission

Radiant UV energy in the 185 to
260 nm band and IR energy at 880
nm.

Basic Operation

Hold the Tester between 2 and 20 feet from the
Detector to be tested. Aim the Tester at the
Detector and press the button. The Red LED
will flash on and off and after approximately 3
seconds the detector will report an alarm. Note
that the detector must be in normal operation
(see the Detector's User Manual).

Advertising