Commercial gas water heater, Sample specifications, Sandblaster – State Industries SDV80-140 User Manual

Page 2: Force, Venting system requirements, Water heaters

Advertising
background image

WATER HEATERS

BTU Input

First Hour

Approx.

Per Hour

Delivery

Recovery

Dimensions in Inches

Shipping

Gal.

Gas

Weight

Model Number

Cap.

Natural

Propane 100° Rise 80° 100° 140°

A

B

C

D

E

F

G

H

I

Conn.

(lbs.)

SDV75 70NE

75

70,000 –

117

81

64

46

69

5

8

61

5

8

26

16

5

8

3

2

54

1

2

˝

352

SDV75 70PE

75

– 65,000

112

74

59

42

69

5

8

61

5

8

26

16

5

8

3

2

54

1

2

˝

352

SDV80 140NE•

80

140,000 140,000

200

180

144

103

76

1

4

71

7

8

28

8

3

4

3

20

1

4

61

5

8

2

1

4

56

5

8

3

4

˝

645

SDV100 199NE*

100

199,000 –

276

258 206

147

74

7

8

70

1

2

30

1

4

8

3

4

3

20

1

4

60

1

8

2

1

4

55

1

8

3

4

˝

825

SDV100 199PE*

100

– 190,000

266

245 196

140

74

7

8

70

1

2

30

1

4

8

3

4

3

20

1

4

60

1

8

2

1

4

55

1

8

3

4

˝

825

SDV100 260NE•

100

260,000 260,000

338

335 268 191

79

1

2

77

1

2

30

1

4

8

3

4

4

19

3

4

61

1

2

2

1

4

56

3

4

˝

900

SDV100 260NE ASME•

100

260,000 260,000

338

335 268 191

79

1

2

77

1

2

30

1

4

8

3

4

4

19

3

4

61

1

2

2

1

4

56

3

4

˝

1010

SDV100 400NE

95

390,000 390,000

461

493 395 282

82

1

4

80

1

4

30

1

4

8

3

4

4 or 6

+

21

3

4

63

1

2

2

1

4

58

1˝**

900

SDV100 400NE ASME

95

390,000 390,000

461

493 395 282

82

1

4

80

1

4

30

1

4

8

3

4

4 or 6

+

21

3

4

63

1

2

2

1

4

58

1˝**

1100

First-Hour Delivery and Recoveries are rounded to nearest gallon.
Model SDV75 70 has

3

4

-inch water connections; all others have 1

1

2

-inch.

Dimensions are rounded to nearest

1

4

-inch.

When ordering propane, change “N” to “P” in model number (SDV80 140PE).
All models available in Canada. When ordering, add “CGA” to model number
(SDV75 70NE CGA).

500 Lindahl Parkway, Ashland City,TN 37015

Commercial Gas Water Heater

Sandblaster

®

Force

gas water heaters are design certified by the CSA International as

Automatic Circulating and Automatic storage water heaters. When used singly or in
manifolded multiples with additional heaters or storage tanks, they can provide an
independent hot water system. When installed with a mixing valve, they can provide both
140°F general use hot water and 180°F sanitizing hot water simultaneously.

SDV80 140, SDV100 199, SDV100 260 and SDV100 400 models meet or exceed Federal
Efficiency Requirements prescribed by the Energy Policy and Conservation Act of 1992
(EPACT) for commercial water heaters. They also meet or exceed ASHRAE 90.1b-1992.

SDV75 70 meets or exceeds Federal Energy Efficiency Standards effective January 1,
1990, according to the National Appliance Energy Conservation Act (NAECA) of 1987.

EC/SDV1/0601

©2001 State Industries, Inc.

Printed in U.S.A.

Venting System Requirements

1 The water heater requires its own (separate) venting system.
2 Venting cannot be connected to existing vent piping or chimney.
3 Venting may terminate vertically or horizontally to the outdoors.
4 Vertical and horizontal vent runs must be secured at 3

1

2

´ intervals.

5 Vent piping cannot under any circumstances be run downhill.
6 Horizontal runs require a minimum

1

4

˝ rise per foot.

7 Vent pipes must be installed so that they can be visually inspected.

SDV Series

Maximum Equivalent Feet of Pipe With One 90° Elbow

Models

3" Schedule 40 PVC

4" Schedule 40 PVC*

6" Schedule 40 PVC*

SDV75-70

50'

N/A

N/A

SDV80-140

135'

N/A

N/A

SDV100-199

135'

N/A

N/A

SDV100-260

N/A

135'

N/A

SDV100-400*

N/A

45'*

110'*

*The first 10 feet of exhaust vent run connected to this model must be run in CPVC or equivalent. The intake air

may be all PVC.

NOTE: Each 90° elbow is equivalent to 5 feet of pipe. Two 45° elbows are equivalent to 5 feet of pipe.

I

C

E

EXHAUST

AIR
INTAKE

B A

D

H

Gas water heater(s) shall be a State Industries, Inc. Sandblaster Force, Model Number,
____________________, with a

gallon storage capacity, an input rate of

Btu/Hour

gas, and a recovery rate of

gallons per hour at a

degree Fahrenheit temperature rise.

Unit(s) shall be direct-vent design, with an automatic blower-powered, two pipe air intake and
exhaust system communicating directly with the outside of the building;. The blower shall have
a safety device that will not allow the operation of the pilot and main burners unless the blower
is in operation. Unit(s) shall have a combustion air passage that is internal to the outer jacket
of the water heater other than the intake and exhaust connections at the top of the water heater.
The units shall be equipped with an Intermittent Electronic Ignition control requiring an external
120 Volt power supply with a rating of 12 amps or less. The control system shall shut off the
gas supply to the unit within 4 seconds if the gas supply or pilot flame are interrupted. The tank
shall be additionally protected against premature failure in the following ways:

1. A

-year limited warranty against failure due to corrosion, metal fatigue or overheating

caused by the buildup of scale, film or other sediment.

2. Against electrolytic corrosion by multiple, factory-installed magnesium anodes.

3. Against failure due to overheating caused by the buildup of scale, film and other sediment
by a construction which incorporates an annular ring, which fits inside the tank at the base. The
ring shall be equipped with a group of calibrated jets, properly positioned so that they will direct
the flow of inlet water in such a way that microscopic particles of precipitated solids shall be
kept in suspension and exhausted from the water heater on that or successive hot water draws.

The burner(s) shall have an individual orifice for each burner tube and be constructed of tubular
aluminized or stainless steel mounted in an easily removable tray.

Water heater(s) shall have the CSA International seal of certification, a working pressure of 150 psi, a
factory-installed ASME rated temperature and pressure relief valve, and a 4˝ x 5˝ tank inspection port.

Sandblaster

®

Force

Sample Specifications

SDV75 70

SDV80 140, SDV100 199, SDV100 260 & SDV100 400

Manufactured under one or more of the
following U.S. Patent Numbers: 4,157,077;
4,263,879; 4,447,377; 4,527,543 and other
patents pending. Canadian Patent Numbers
1,151,480; 1,215,276 and other Canadian
patents pending.

In keeping with our policy of continuous product
improvement, specifications are subject to
change without prior notice.

COLD INLET

HOT

OUTLET

*Rear plumbing.
**Gas connection on Propane models is

3

4

-inch.

ASME construction not available.

•NSF construction available, add 5˝ to height and

add NSK to model number (SDV80 140NE NSK).

+

Vent diameter depends on length of run. 4 ˝ diameter
up to 40 equivalent feet each run.

Advertising
This manual is related to the following products: