Troubleshooting the millivolt control system – Superior DIRECT-VENT GAS FIREPLACES SDV35 User Manual

Page 23

Advertising
background image

23

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

1. Spark igniter will not light pilot after

repeated triggering of igniter button.

WARNING: if the pilot will not light

after 1 minute of attempting, wait

for at least 5 minutes for gas to

clear before attempting again.

A. Defective igniter

(no spark at electrode).

Check for spark at electrode and pilot; if no spark

and electrode wire is properly connected, replace

igniter.

B. Defective or misaligned electrode at pilot

(spark at electrode).

Using a match, light pilot. If pilot lights, turn off pilot

and trigger the igniter button again. If pilot lights, an

improper gas mixture caused the bad lighting and a

longer purge period is recommended. If pilot will not

light – check gap at electrode and pilot – should be 1/8"

to have a strong spark. If gap does not measures 1/8",

replace pilot (see Figure 10 or 11 on Page 15).

C. Gas supply pressure errant.

Check inlet gas pressure. It should be within the limits

as marked on the rating plate.

D. Pilot orifice plugged.

Clean or replace pilot orifice.

2. Pilot will not stay lit after

carefully following the lighting

instructions.

A. Defective pilot generator

(thermocouple).

Check pilot flame, it must impinge on thermocouple

(see Figure 10 or 11 on Page 15). Clean and/or adjust

pilot for maximum flame impingement on thermo-

couple. Ensure that the connection between the valve

and thermocouple are tight and secure.

3. Pilot burning, no gas to burner, Valve

knob “ON,” and the (optional) burner

ON/OFF switch is “ON." Read impor-

tant note below.

IMPORTANT NOTE: If an optional

*remote switch is used for burner

operation, the unit-mounted burner

OFF/ON switch (if installed) must be

in the "OFF" position.

*Optional remote switch kits - wall

switch, wall thermostat or remote

control.

A. Wall switch or wires defective.

Check wall switch and wires for proper connections.

Jumper wire across terminals at wall switch, if burner

comes on, replace defective wall switch. If okay, jumper

wires across wall switch wires at valve, if burner comes

on, wires are faulty or connections are bad.

B. Thermopile may not be generating suf-

ficient millivolts.

Check thermopile with millivolt meter. Take reading

at thermopile terminals of gas valve. Should read

325 millivolts minimum with optional wall switch

“OFF.” Replace faulty thermopile if reading is below

specified minimum.

C. Plugged burner orifice.

Check burner orifice for blockage and remove.

D. ON/OFF Switch & *Remote Switch are in

the "ON" position resulting in excessive

resistance.

When turning on the burner using a *remote switch,

ensure that the optional ON/OFF switch is in the "OFF"

position. If both switches are in the ON position, it may

result in excessive resistance (and millivolt drainage)

and the burner may not come on.

4. Frequent pilot/burner outage prob-

lem.

A. Pilot flame may be too low or blowing

(high) causing the pilot/valve safety to drop

out.

Clean and/or adjust pilot flame for maximum flame

impingement on thermocouple (Figure 10 or 11 on

Page 15).

* Optional remote switch kits - wall switch, wall thermostat or remote control.

TROUBLESHOOTING THE MILLIVOLT CONTROL SYSTEM

Note: Before troubleshooting the gas control system, Ensure external gas shut off valve, located at gas supply inlet, (and

wall switch, iff applicable), is in the “ON” position.

Important: Valve system troubleshooting should only be accomplished by a qualified service technician.

Advertising