Applications, Siemens building technologies, inc. 15 – Siemens BACNET 125-699 User Manual

Page 23

Advertising
background image

Applications

Siemens Building Technologies, Inc.

15

TEC2574CDR1

FAN

ELECTRIC

HEAT

(OPTIONAL)

COIL

HEATING /

COOLING

COIL

WATER

SOURCE

COMPRESSOR 2

REVERSING

VALVE*

SUPPLY AIR

O.A.
N.C.

R.A.

N.O.

* CONTROLLED INTERNALLY BY THE HEAT PUMP

** THE O.A. AND R.A. DAMPERS MUST
BE MECHANICALLY LINKED.

R.A.

DAMPER**

(OPTIONAL)

MIXED AIR

TEMPERATURE

SENSOR

(OPTIONAL)

COMPRESSOR 1

REVERSING

VALVE*

COIL

COIL

O.A.

DAMPER**

(OPTIONAL)

FLN TRUNK
AO1 (0-10V)
DO1
DO2
DO3
DO4
DO5
DO6
DO7
DO8
DI3/AI3
DI4/AI4
DI5/AI5
DI2
DI6
AO2 (0-10V)
AO3 (0-10V)
RTS

N.O.

HEAT PUMP

CONTROLLER -

MULTI-STAGE

RTS

WALL

SWITCH

(OPTIONAL)

ELECTRIC HEAT (OPTIONAL)
1ST HEATING COMPRESSOR

2ND HEATING COMPRESSOR

1ST COOLING COMPRESSOR

2ND COOLING COMPRESSOR

FAN

SPARE AI (0-10V or 4-20mA) OR SPARE DI (DRY CONTACT)

SPARE AI (10K THERMISTOR) OR SPARE DI (DRY CONTACT)

MIXED AIR TEMPERATURE SENSOR 10K THERMISTOR (OPTIONAL)

HEAT PUMP ALARM (OPTIONAL)

24 V-AC

*

ON BOARD, AO1 IS GROUPED PYSICALLY WITH AO2 AND AO3

*

Figure 6. AppIication 2584 Control Drawing.