Siemens OpenAir GND Series User Manual

Openair™ gnd series electronic damper actuator, Technical instructions

Advertising
background image

Technical Instructions

Document No. 155-746

EA GND-1

March 17, 2005

OpenAir™ GND Series Electronic Damper Actuator

UL Listed Fire/Smoke and Smoke Control Dampers
2-Position, 15-second Run Time,
15-second Spring Return Time

N474

Description

The OpenAir™ direct coupled, fast-acting, two-position, spring return electronic actuators
are available as 24 Vac/dc, 120 Vac, and 230 Vac models. They are intended for use on
UL listed smoke control dampers and combination fire/smoke rated dampers.

Features

• Optional built-in auxiliary switches: Fixed switch points at 5° and 85 ° rotation.
• Optional built-in Electronic Fusible Link (EFL) capability with four temperature

ratings: 165°F (74°C), 212°F (100°C), 250°F (121°C), 350°F (177°C).

• Reversible fail-safe spring return.
• All metal housing.
• Pre-cabled Teflon® insulated lead wires.
• Fifteen-second operation at rated torque, temperature and voltage.

Application

This actuator is used for the control of dampers requiring up to 53 lb-in (6Nm) driving
torque. It is intended for control of UL listed smoke control dampers and combination
fire/smoke HVAC dampers. This actuator is designed to meet the 2002 revisions to the
UL 555/555S and the AMCA Standard 520 specifications.