PIPING A HEATING - COOLING SYSTEM TO A WATER
BOILER AND CHILLER

The chiller must be piped in parallel with the boiler. Figure below

illustrates a method of piping a heating-cooling system to a

water boiler and a chiller. Hand valves (shown) or automatic

valves must be installed to prevent circulation of chilled water in

the boiler or hot water in the chiller.

The air control system and pressure control system must oper-

ate with chiller only, or the boiler only, being valved to the piping

system.

Separate control devices on the boiler and chiller may be used,

or a single set of air and pressure controls on the common pip-

ing may be preferred.

If the boiler is used to supply hot water to heating coils in air

handling units, flow control valves or other devices must be

installed to prevent gravity circulation of water in the coils dur-

ing the cooling cycle.

IF REPLACEMENT PARTS ARE NEEDED

When parts are needed, refer to boiler model and serial num-

ber shown on the boiler name/rating plate. Refer to publication

number S-10PL Sentry Replacement Parts for part numbers.

Whenever possible refer to the original order by number and

date.

Control identification and replacement should not be attempted

by unskilled personnel. Only simple, easily-identified controls

and parts may be obtained locally. All other controls and

parts should be identified by and ordered from Slant/Fin.

Relief/Safety valves must be ASME rated for the pressure and

gross output of the boiler.

For replacement parts, heating contractors should contact their

Slant/Fin boiler distributor.