5 programming – Studer Innotec C3548 COMPACT User Manual

Page 19

Advertising
background image

STUDER INNOTEC

COMPACT

COMPACT

COMPACT

COMPACT

User manual

COMPACT V2.0 E

19

4.11 The Temperature sensor

Operating voltage of lead-acid batteries change depending on the temperature. To correct the
operating voltages according to the actual temperatures, a temperature sensor can be connected
to the COMPACT.
The compensation through the sensor is –3mV/°C/Cell.

Order Number: CT-35
Dimensions: H x B x T / 58 x 51.5 x 22mm

5 Programming:

5.1 Standard

setting

The COMPACT is delivered with the default setting following:

5.1.1 Working

mode

The working of the charger, the inverter and the transfer are describe in chapter 5.3/5.4/5.5.

5.1.2 Battery

voltage

Low voltage

11.6V / 23.2V / 46.4V

Float Charge

13.5V / 27.0V / 54.0V

End of Charge Voltage

14.4V / 28.8V / 57.6V

Equalization

15.3V / 30.6V / 61.2V

Absorption Time:

2 Hours

5.1.3 Auxiliary

contact

Active in case of defect or manual turn off with the LED 10/11/12/13

5.2 Reset

value

When the COMPACT is to be connected to a battery or after an interruption (RESET), it is always
programmed with these standard settings..
In order to get to these settings during operation you must press the three Push Buttons 20/21/22
simultaneously for a minimum of 2 seconds.

5.3 Battery voltages and absorption time:

The voltage levels (low voltage, float charge, end of charge and equalization ) and the duration of
the absorption charge can be changed.
The display of these voltages and the times in the program mode are in accordance with the
diagram shown below:

5.3.1 Table of voltage and timing threshold

Low

voltage

LED 13

Float Charge

LED 12

Absorption

LED 11

Equalization

LED 10

Absorpt.

Time

LED 10->13

LED 12V 24V 48V 12V 24V 48V 12V 24V 48V 12V 24V 48V

12/24/48V

14 12.0 24.0 48.0 13.7 27.4 54.8 16.2 32.4 64.8 16.2 32.4 64.8

4

h

15 11.8 23.6 47.2 13.6 27.2 54.4 15.6 31.2 62.4 15.9 31.8 63.6

3

h

16 11.6 23.2 46.4 13.5 27.0 54.0

15 30 60 15.6 31.2 62.4

2

h

17 11.4 22.8 45.6 13.4 26.8 53.6 14.4 28.8 57.6 15.3 30.6 61.2

1

h

18 11.2 22.4 44.8 13.3 26.6 53.2 14.2 28.4 56.8

15 30 60

0

1Min.

The heavy printed values show the standard settings.