Operation, Caution – SPX Cooling Technologies Marley MH 05-116E User Manual

Page 19

Advertising
background image

19

When the use of industrial antifreeze solutions is not possible, the system
must be operated to meet both of the following conditions.

1. Maintain sufficient flow rate through the coil.

2. Maintain sufficient heat load on the process fluid. Fluid exiting the

coil must be maintained at or above 45°F. Cycling of the recirculation
pump should not be used to control process temperatures.

Draining the coil is not acceptable as a normal method of freeze
protection—draining promotes corrosion inside the coil tubes. Drain-
ing is acceptable in an emergency if the coil is not protected by an
antifreeze solution.

It is recommended that you discuss your freeze prevention options with
your local Marley sales representative.

Operation

Model

Coil Volume

US Gallons

Model

Coil Volume

US Gallons

MHF702__061

65

MHF705__061

235

MHF702__081

85

MHF705__081

315

MHF702__101

105

MHF705__101

390

MHF702__121

125

MHF705__121

465

MHF702__062

75

MHF705__062

285

MHF702__082

100

MHF705__082

380

MHF702__102

120

MHF705__102

470

MHF702__122

150

MHF705__122

565

MHF703__061

85

MHF706__061

390

MHF703__081

115

MHF706__081

500

MHF703__101

140

MHF706__101

610

MHF703__121

170

MHF706__121

725

MHF703__062

100

MHF706__062

475

MHF703__082

130

MHF706__082

610

MHF703__102

165

MHF706__102

750

MHF703__122

200

MHF706__122

885

MHF704__061

160

MHF707__061

450

MHF704__081

210

MHF707__081

580

MHF704__101

260

MHF707__101

710

MHF704__121

310

MHF707__121

840

MHF704__062

190

MHF707__062

570

MHF704__082

250

MHF707__082

740

MHF704__102

315

MHF707__102

905

MHF704__122

375

MHF707__122

1071